The control panel with factory settings (new one or one after restart of settings) supports all
keypads connected to the bus. It does not, however, control the status of keypad zones and
tamper contacts, and does not provide for programming the security system parameters.
Prior to programming the system, you should:
1. Set individual, correct addresses in keypads.
2. Start the keypad identification function (S
ERVICE MODE
Æ
S
TRUCTURE
Æ
H
ARDWARE
Æ
I
DENTIFICATION
Æ
LCD
KEYPADS ID
.).
3. Start the expander identification function (S
ERVICE MODE
Æ
S
TRUCTURE
Æ
H
ARDWARE
Æ
I
DENTIFICATION
Æ
E
XPANDERS ID
.).
5. Compliance with CLC/TS 50131-3 requirements
To meet the requirements of CLC/TS 50131-3:
•
for each detector provided with the antimasking function, reserve two control panel zones:
a supervision zone, to register violations of the detector, and a technical one, to register
triggering of the antimasking feature. If the "maximum zone violation time" programmed for
the technical zone is shorter than the antimasking relay cut-off time, a detector trouble will
be reported at an attempt to cover the detector;
•
for all the expansion modules with integrated power supplies, an additional supervised
overcurrent protection (like the ZB-2) must be used for each power supply output.
Overload signaling output (OVL) should be connected to zone programmed as type 62
(T
ECHNICAL
–
O
VERLOAD
).