INTEGRA Installer
Manual
19
number of wires in signal cable
distance between module and
control panel
CK / CK1 / CK2
DT / DT1 / DT2
COM
up to 300 m
1
1
1
300 – 600 m
2
2
2
600 – 1000 m
2
2
4
Table 3.
Note:
Signal wires (DT, CK and COM) must be run in one cable!
The modules without power supply unit may be powered directly from the control panel if the
distance between control panel and module is not higher than 300 m. Where distances are
small (up to 100 m), the modules without power supply unit may be connected one after the
other to one supply cable (see Fig. 13). If this is the case, devices connected to the
expanders must be independently supplied (by means of a separate cable from the control
panel, expander with power supply, or a power supply unit). Where the distance between the
control panel and the modules exceeds 300 m, the modules without power supply unit should
not be supplied from the control panel. They should have an independent supply source
(a power supply unit or an expander with power supply).
Z1 COM Z2
Z3
Z4
Z5
Z6
Z7
Z8
COM
COM
COM
TMP
COM
CLK
DAT
+12V
+12V
CA-64 E
COM
CLK
DAT
+12V
COM +EX1 DT1 CK1
CKM
COM +EX2 DT2 CK2
COM +KPD DTM
OUT4
COM
Z1 COM Z2
Z3 COM Z4
Z5
INTEGRA 64 / INTEGRA 128
Fig. 11. Connection of the expansion module without power supply by the example of the
CA-64 E zones expander and the INTEGRA 64 / INTEGRA 128 control panel. The housing
tamper contact is connected to the TMP and COM terminals.