41
Parameter
Offset
Type
R/W
Range
Log parameter #10 ID
+9
UINT16
R/W
See Table 5-2
Log parameter #11 ID
+10
UINT16
R/W
See Table 5-2
Log parameter #12 ID
+11
UINT16
R/W
See Table 5-2
Log parameter #13 ID
+12
UINT16
R/W
See Table 5-2
Log parameter #14 ID
+13
UINT16
R/W
See Table 5-2
Log parameter #15 ID
+14
UINT16
R/W
See Table 5-2
Log parameter #16 ID
+15
UINT16
R/W
See Table 5-2
1. Parameters that can be selected for data log are listed in Table 5-2. Before setting up the parameters for any data log, the
memory partition must be allocated for the log (see Section 5.19). When writing the data log setup registers, only
parameters that are specified in the partition record setup will be written. When reading registers, those that are not defined
in the data log setup will be read as zeros.
2. If a partition has been allocated as a TOU profile log partition, the data log setup for the partition cannot be written. Write
requests will be ignored. A read request will return identifiers of the TOU season tariff energy registers 28672 to 28687.
5.21 Real Time Clock Registers
Table 5-47 RTC Registers
Parameter
Register
Type
R/W
Range
Seconds 4352
UINT16
R/W
0-59
Minutes
4353
UINT16
R/W
0-59
Hour
4354
UINT16
R/W
0-23
Day of month
4355
UINT16
R/W
1-31
Month
4356
UINT16
R/W
1-12
Year 4357
UINT16
R/W
0-99
Day of week
4358
UINT16
R/W
1-7 (1=Sunday)
The day of week is not checked when written. It is set automatically when you change the date.
5.22 Time Zone Information Registers
Table 5-48 Time Zone Registers
Parameter
Register
Type
R/W
Range
Daylight savings time (DST) option
4320
UINT16
R/W
0 = disable DST (use standard time only),
1 = enable DST
DST start month
4321
UINT16
R/W
1 - 12
DST start week of the month
4322
UINT16
R/W
1 - 4 = 1st, 2nd, 3rd and 4th week,
5 = the last weekday in the month
DST start weekday
4323
UINT16
R/W
1-7 (1= Sun, 7 = Sat)
DST end month
4324
UINT16
R/W
1 - 12
DST end week of the month
4325
UINT16
R/W
1 - 4 = 1st, 2nd, 3rd and 4th week,
5 = the last weekday in the month
DST end weekday
4326
UINT16
R/W
1-7 (1= Sun, 7 = Sat)
5.23 Communications Password Register
Table 5-49 Password Register
Parameter
Register
Type
R/W
Range
Communications password
2575
UINT16
R/W
Write: 0 to 65535
Read:
0 = access permitted
65535 = authorization required