Parameter
UINT16
INT32
Point
R/W
Unit
2
Range/Scale
1
Reg.
Conv.
ID
Low
High
Generic TOU season tariff energy registers - only as a reference for TOU profile logs
Season tariff #1 register
0x7000 R
0
10
9
-1
Season tariff #2 register
0x7001 R
0
10
9
-1
...
...
Season tariff #16 register
0x700F R
0
10
9
-1
Generic TOU season tariff maximum demand registers - only as a reference for TOU profile logs
Season tariff #1 register
LIN3
0x7100 R
0
Pmax
Season tariff #2 register
LIN3
0x7101 R
0
Pmax
...
...
Season tariff #16 register
LIN3
0x710F R
0
Pmax
Setpoint status (bitmap)
9
Setpoints
status
27648-27649
0x7C00
R
1
For the parameter limits, see Note
1
to Table 5-1.
2
When using direct wiring (PT Ratio = 1), voltages are transmitted in 0.1 V units, currents in 0.01 A units, and powers in
0.001 kW/kvar/kVA units. For wiring via PTs (PT Ratio > 1), voltages are transmitted in 1V units, currents in 0.01 A units,
and powers in 1 kW/kvar/kVA units.
3
The actual frequency range is 45.00 - 65.00 Hz.
4
Absolute min/max value (lag or lead).
5
The exported energy registers are read as positive unsigned long (32-bit) integers.
6
When the 4LN3 or 3LN3 wiring mode is selected, the voltages will be line-to-neutral; for any other wiring mode, they will be
line-to-line voltages.
7
When the 4LN3, 4LL3 or 3LN3 wiring mode is selected, the harmonic voltages will be line-to-neutral; for any other wiring
mode, they will be line-to-line voltages. The line-to-line harmonic voltages in the 3DIR2, 3LL3 and 2LL1 wiring modes, and the
L31 harmonic voltage in the 3OP2 and 3OP3 wiring modes will be calculated accurately if the voltages are balanced.
8
Phase angles are referenced to Voltage V1 in 4-wire (4LN3, 4LL3, 3LN3 and 3LL3 wiring modes), and to Voltage V12 in 3-
wire connections (3DIR2, 3OP2 and 3OP3 wiring modes). Available in Version 4.88.3 or later.
9
Available starting with Version 4.88.2 or later.
M These parameters are recorded to the Min/Max log
NOTE:
Power demand and energy registers are only available in the PM172E. In the PM172P, they are read as zeros.
5.3 Min/Max Log Registers (32-bit)
Table 5-3 Min/Max Log Registers
Parameter
Registers
Type
Minimum real-time values per phase
Min. Voltage L1/L12
35840-35841
INT32
Timestamp 35842-35843
UINT32
Min. Voltage L2/L23
35844-35845
INT32
Timestamp 35846-35847
UINT32
Min. Voltage L3/L31
35848-35849
INT32
Timestamp 35850-35851
UINT32
Min. Current L1
35852-35853
INT32
Timestamp 35854-35855
UINT32
Min. Current L2
35856-35857
INT32
Timestamp 35858-35859
UINT32
Min. Current L3
35860-35861
INT32
Timestamp 35862-35863
UINT32
Reserved 35864-35911
Min. Voltage THD L1/L12
35912-35913
INT32
Timestamp 35914-35915
UINT32
Min. Voltage THD L2/L23
35916-35917
INT32
Timestamp 35918-35919
UINT32
Min. Voltage THD L3/L31
35920-35921
INT32
Timestamp 35922-35923
UINT32
Min. Current THD L1
35924-35925
INT32
Timestamp 35926-35927
UINT32
Min. Current THD L2
35928-35929
INT32
Timestamp 35930-35931
UINT32
Min. Current THD L3
35932-35933
INT32
Timestamp 35934-35935
UINT32