35
Parameter
Offset
Type
Range
Reserved
+26, 27
UINT16
0 (N/A)
Operate limit
+28, 29
INT32
see Table 5-32
Release limit
+30, 31
INT32
see Table 5-32
Action #1
Action type
+32
UINT16
see Table 5-33
Action target
+33
UINT16
see Table 5-33
Action #2
Action type
+34
UINT16
see Table 5-33
Action target
+35
UINT16
see Table 5-33
Action #3
Action type
+36
UINT16
see Table 5-33
Action target
+37
UINT16
see Table 5-33
Action #4
Action type
+38
UINT16
see Table 5-33
Action target
+39
UINT16
see Table 5-33
Delays Reserved
+40 UINT16
0
(N/A)
Operate delay
+41
UINT16
0-9999 (x 0.1 sec)
Release delay
+42
UINT16
0-9999 (x 0.1 sec)
Reserved
+43
UINT16
0
(N/A)
1.
The setpoint is disabled when the first trigger ID is set to NONE. To disable the setpoint, write zero into this register.
2.
When writing the setpoint registers (except the event when the setpoint is to be disabled), it is recommended to write
all the setpoint registers using a single request, or disable the setpoint before writing into separate registers. Each
value being written is checked for compatibility with the other setpoint parameters; if the new value does not conform
to these, the request will be rejected.
3.
Operate and release limits for the trigger parameters and their conversion scales are indicated in Table 5-29. Each
limit value occupies two contiguous registers, the first of which (low word) contains the limit value, and the second
(high word) is reserved for long parameters. This register is always read as zero. When written, its value is ignored.
4.
Limits indicated in Table 5-29 by a N/A mark are read as zeros. When writing, they can be omitted or should be
written as zeros.
5.
When a setpoint action is directed to a relay allocated to output energy pulses, an attempt to re-allocate it for a
setpoint will result in a negative response.
Table 5-32 Setpoint Trigger Parameters
Trigger parameter
Trigger
Type
Unit
2
Limit/scale
1
Con-
ID
Low
High
version
None
None
0x0000
UINT16
N/A N/A NONE
Internal events
E
kWh import pulse
0x0400 UINT16
N/A N/A NONE
kWh export pulse
0x0401 UINT16
N/A N/A NONE
kvarh import pulse
0x0403 UINT16
N/A N/A NONE
kvarh export pulse
0x0404 UINT16
N/A N/A NONE
kvarh total pulse
0x0405 UINT16
N/A N/A NONE
kVAh total pulse
0x0406 UINT16
N/A N/A NONE
Start new demand interval
0x0407 UINT16
N/A N/A NONE
Start new tariff interval
0x0408 UINT16
N/A N/A NONE
Start new volt/ampere demand interval
0x0409 UINT16
N/A N/A NONE
Start new sliding window demand interval
0x040A UINT16
N/A N/A NONE
Timers
E
Timer #1
0x0500 UINT16
N/A N/A NONE
Timer #2
0x0501 UINT16
N/A N/A NONE
Status inputs
Status input #1 ON
0x0600 UINT16
N/A
N/A
NONE
Status input #2 ON
0x0601 UINT16
N/A
N/A
NONE
Status input #1 OFF
0x8600 UINT16
N/A
N/A
NONE
Status input #2 OFF
0x8601 UINT16
N/A
N/A
NONE
Pulse inputs
E
Pulse input #1
0x0700 UINT16
N/A N/A NONE
Pulse input #2
0x0701 UINT16
N/A N/A NONE
Relay status
7
Relay #1 ON
0x0800 UINT16
N/A
N/A
NONE
Relay #2 ON
0x0801 UINT16
N/A
N/A
NONE
Relay #1 OFF
0x8800 UINT16
N/A
N/A
NONE