34
NOTES
1.
All digital inputs that were not allocated as pulse inputs will be automatically configured as status inputs.
2.
A digital input allocated for the external demand synchronization pulse or time synchronization pulse will be
automatically configured as a pulse input.
Table 5-28 Digital Inputs Allocation Mask
Bit
Description
0
Digital input # 1 allocation status
1
Digital input # 2 allocation status
2-15
Not used (read as 0)
Bit meaning: 0 = input is not allocated, 1 = input is allocated to the group
5.14 Timers Setup Registers
Table 5-29 Timers Setup Registers
Parameter
Register Type
R/W
Range
Timer #1 time interval
3300
UINT16 R/W
1-9999 sec, 0 = timer disabled
Timer #2 time interval
3301
UINT16 R/W
1-9999 sec, 0 = timer disabled
5.15 Alarm/Event Setpoints Registers
Table 5-30 Setpoint Registers
Setpoint
Setup registers (see Table 5-31)
Setpoint #1
352-395
Setpoint #2
396-439
Setpoint #3
440-483
Setpoint #4
484-527
Setpoint #5
528-571
Setpoint #6
572-615
Setpoint #7
616-659
Setpoint #8
660-703
Setpoint #9
704-747
Setpoint #10
748-791
Setpoint #11
792-835
Setpoint #12
836-879
Setpoint #13
880-923
Setpoint #14
924-967
Setpoint #15
968-1011
Setpoint #16
1012-1055
Table 5-31 Setpoint Setup Registers
Parameter
Offset
Type
Range
Condition #1
Logical operator
+0
UINT16
0 = OR
Trigger ID
+1
UINT16
see Table 5-32
Reserved
+2, 3
UINT16
0 (N/A)
Operate limit
+4, 5
INT32
see Table 5-32
Release limit
+6, 7
INT32
see Table 5-32
Condition #2
Logical operator
+8
UINT16
0 = OR, 1 = AND
Trigger ID
+9
UINT16
see Table 5-32
Reserved
+10, 11
UINT16
0 (N/A)
Operate limit
+12, 13
INT32
see Table 5-32
Release limit
+14, 15
INT32
see Table 5-32
Condition #3
Logical operator
+16
UINT16
0 = OR, 1 = AND
Trigger ID
+17
UINT16
see Table 5-32
Reserved
+18, 19
UINT16
0 (N/A)
Operate limit
+20, 21
INT32
see Table 5-32
Release limit
+22, 23
INT32
see Table 5-32
Condition #4
Logical operator
+24
UINT16
0 = OR, 1 = AND
Trigger ID
+25
UINT16
see Table 5-32