5.8 Basic Setup Registers
Table 5-19 Basic Setup Registers
Parameter
Register
Type
R/W
Range
Wiring mode
1
2304
UINT16 R/W
0 = 3OP2, 1 = 4LN3, 2 = 3DIR2,
3 = 4LL3, 4 = 3OP3, 5 = 3LN3, 6 = 3LL3,
7 = 2LL1, 8=3BLN3, 9=3BLL3,
10=2LN3
PT ratio
2305
UINT16 R/W
10 to 65000
×
0.1
CT primary current
2306
UINT16 R/W
1 to 10000 A
Power demand period
E
2307
UINT16
R/W
1,2,5,10,15,20,30,60 min,
255 = external synchronization
2
Volt/ampere demand period
2308
UINT16 R/W
0 to 1800 sec
Averaging buffer size
2309
UINT16 R/W
8, 16, 32
Reset enable/disable
2310
UINT16 R/W
0 = disabled, 1 = enabled
Reserved
2311
UINT16 R
Read as 65535
The number of demand periods
E
2312
UINT16 R/W
1 to 15
Reserved
2313
UINT16 R
Read as 65535
Nominal frequency
2315
UINT16 R/W
50, 60 Hz
Maximum demand load current
2316
UINT16 R/W
0 to 10000 A (0 = CT primary current)
1
The wiring mode options are as follows:
3OP2 - 3-wire open delta using 2 CTs (2 element)
4LN3 - 4-wire WYE using 3 PTs (3 element), line-to-neutral voltage readings
3DIR2 - 3-wire direct connection using 2 CTs (2 element)
4LL3 - 4-wire WYE using 3 PTs (3 element), line-to-line voltage readings
3OP3 - 3-wire open delta using 3 CTs (2 1/2 element)
3LN3 - 4-wire WYE using 2 PTs (2 1/2 element), line-to-neutral voltage readings
3LL3 - 4-wire WYE using 2 PTs (2 1/2 element), line-to-line voltage readings
2LL1 - 2-wire line-to-line connection using 1 PT (1 element)
3BLN3 -
3BLL3 -
2LN3 - 4-wire WYE using 2 PTs (2 element), 3 CTs (3 element), line-to-neutral voltage readings
2
Synchronization of power demand interval can be made through a digital input.
E
Available in the PM172E.
5.9 User Selectable Options Setup Registers
Table 5-20 User Selectable Options Registers
Parameter
Register
Type
R/W
Range
Power calculation mode
2376
UINT16
R/W
0 = using reactive power,
1 = using non-active power
Energy roll value
1, E
2377
UINT16
R/W
0 = 1
×
104
1 = 1
×
105
2 = 1
×
106
3 = 1
×
107
4 = 1
×
108
5 = 1
×
109
Phase energy calculation mode
E
2378 UINT16
R/W
0 = disabled, 1 = enabled
Analog output option
2379
UINT16
R/W
0 = none
1 = 0-20 mA
2 = 4-20 mA
3 = 0-1 mA
4 =
±
1 mA
Analog expander output
2
2380
UINT16
R/W
0 = none
1 = 0-20 mA
2 = 4-20 mA
3 = 0-1 mA
4 =
±
1 mA
Battery 2381
UINT16
R/W
0 = OFF, 1 = ON
1
For short energy registers (see Table 5-1), the maximum roll value will be 1
×
108 for positive readings and 1
×
107 for
negative readings.