Table 5-33 Setpoint Actions
Action
Action type
Action Target
No action
0x00
0x00
Operate relay#1
1
0x30
0x00
Operate relay#2
1
0x30
0x01
Increment counter#1
E
0x40
0x00
Increment counter#2
E
0x40
0x01
Increment counter#3
E
0x40
0x02
Increment counter#4
E
0x40
0x03
Clear counter #1
E
0x41
0x00
Clear counter #2
E
0x41
0x01
Clear counter #3
E
0x41
0x02
Clear counter #4
E
0x41
0x03
Clear all counters
E
0x64
0x00
Reset total energy
E
0x60
0x00
Reset all total maximum demands
E
0x61
0x00
Reset power maximum demands
E
0x61 0x01
Reset volt/ampere maximum demands
E
0x61
0x02
Reset TOU energy
E
0x62
0x00
Reset TOU maximum demands
E
0x63 0x00
Clear Min/Max registers
E
0x65
0x00
Event log
2, E
0x70
0x00
Data log #1
E
0x71
0x00
Data log #2
E
0x71
0x01
Data log #3
E
0x71
0x02
Data log #4
E
0x71
0x03
Data log #5
E
0x71
0x04
Data log #6
E
0x71
0x05
Data log #7
E
0x71
0x06
Data log #8
E
0x71
0x07
1
Operate/release actions via relays are automatically recorded to the event log whenever an electrical quantity, status input,
or phase reversal trigger is used.
2
Either setpoint transition (both operate and release) is recorded to the event log.
E
Available in the PM172E.
5.16 Pulsing Setpoints Registers
Table 5-34 Pulsing Registers
Relay
Setup registers (see Table 5-35)
Relay #1
2892-2893
Relay #2
2894-2895
Table 5-35 Pulsing Setup Registers
Parameter
Offset
Type
R/W
Range
Output parameter ID
+0
UINT16 R/W
see Table 5-36
Number of unit-hours per pulse
+1
UINT16 R/W
1-9999
Table 5-36 Pulsing Output Parameters
Pulsing parameter
ID
None
0
kWh import
1
kWh export
2
kvarh import
4
kvarh export
5
kvarh total (absolute)
6
kVAh total
7
5.17 Relay Operation Control Registers
These registers allow the user to manually override setpoint relay operations. Either relay may be
manually operated or released using commands sent via communications.