Web Interface - Email Alerts
1. Email Recipient -
This field is where the user name of the e-mail recipient is entered. Do not enter the
domain and suffix. If the full address is [email protected], then johnsmith should be entered in this field.
2. Email Domain -
This field is where the user enters the domain name of the email recipient. Do not
enter the user name or the @. If the full address is [email protected], then domain.com should be
entered in this field.
3. Email Server -
This field is where the user enters the address of the local outgoing email server for the
email recipient. Consult with the network administrator for the email server address. Emails are sent using
SMTP.
4. NTP Synchronization Timeout -
When the box is checked, the master clock checks the amount of
time since the last NTP signal has been received. If the amount of time recorded exceeds the amount of
time specified in the box to the right, then the master clock sends an email alert. If this option is selected,
the value in the box should be 1 or higher.
5. GPS Synchronization Timeout -
When the box is checked, the master clock tests the internal GPS
module to confirm that it is receiving a valid time signal from the GPS antenna. If the module fails the
check for an amount of time exceeding the value specified in the box to the right, then the master clock
sends an email alert. If this option is selected, the value in the box should be 1 or higher.
6. Master Restart -
When the box is checked, the master clock sends an email alert every time that it is
restarted (including after power loss or deactivation by the user).
7. Fire Alarm -
When the box is checked, the master clock sends an email whenever the master clock
receives a signal that the fire alarm has been activated. The fire alarm must be properly wired to the master
clock for this to work. For wiring instructions, refer to the section of this manual labeled “Inputs - Sync-
Wire: Fire Alarm Interface Installation.”
8. Submit -
When the button is clicked on, all of the settings on the page are saved and applied.
9. Test Send -
When the button is clicked on, the master clock will send an email to whichever address
has been entered. It does NOT save the settings.