Fault detected
Remote controller display
Indoor protection
Fan motor protection thermostat
P1
Outdoor protection
Fan motor protection thermostat
P2
Compressor protection thermostat
Incorrect discharge temp of PC (AC) comp.
P3 (P17)
High-pressure switch
P4
Indoor protection
Float switch
P10
Indoor sensor
Open/or damaged
F1-F3, F10
Outdoor sensor
Open/or damaged
F4, F5, F7, F25
Compressor
PC comp. motor is overloaded.
H1
protection
PC comp. motor is locked.
H2
AC comp. motor is overloaded.
H11
AC comp. motor is locked.
H12
11-3.
Main Alarm Messages which Indicate Mis-Wiring & Mis-Setting
Cause
• Individual Remote Control
• Remote controller not properly connected.
• Power supply not ON.
• Remote controller not properly connected.
• Wiring connection fault of
indoor/outdoor units
• Power supply of outdoor unit not ON.
• Combination of indoor/outdoor units is wrong.
* Incorrect setting of No. of indoor unit on outdoor control PCB. (S004 setting)
* Power supply of some indoor units not ON.
11-4.
Main Alarm Messages Indicating Unit Malfunction
—
—
P9
(*)
E9
E6
E1
E4
• 2 main remote controllers set.
* Ref: Alarm “P9” is not generated if the remote controller is set at test run.
• Improper wiring connections of ceiling panel
Group Control
Multiple Remote Control
• Wiring connection fault of some indoor/outdoor units inside
the group
●
comp.: Compressor
●
temp.: Temperature
●
PC: Power Control
●
AC: Standard
NOTE
Remote
controller
display
Nothing
displayed