17
S4179544
70, 90 Type
Outdoor Unit
AVOID:
●
heat sources, exhaust fans, etc.
●
damp, humid or uneven locations.
DO:
●
choose a place as cool as possible.
●
choose a place that is well ventilated.
●
allow enough room around the unit for air intake/
exhaust and possible maintenance.
Installation Space
Install the outdoor unit where there is enough space
for ventilation. Otherwise the unit may overheat. Refer
to the figure at right for the minimum space require-
ments regardless of how many units are installed. The
mounting base should be concrete or a similar material
that allows for adequate drainage. Make provisions for
anchor bolts, platform height, and other site-specific
installation requirements.
Do not do any wiring or tubing within 60 cm of the
front panel, because it is needed as a servicing
space for the compressor.
Multiple Installation
Refer to the above diagram when installing more than
1 unit. Take into consideration nearby pedestrian
walkways and ventilation requirements when installing.
*Consult a company that sells the unit about multiple
installation.
Three units placed adjacently
Out-
door
unit
Heat
source
Hot air
Exhaust fan
0024_C_I
Min. 50 cm
Min. 13 cm
Min. 13 cm
Min. 50 cm
Min.
50 cm
Min. 60 cm
on the
valve side
Min. 2 m
0025_C_I
Min. 13 cm
Min. 13 cm
Min. 60 cm
Min. 50 cm
Min. 13 cm
Min. 13 cm
Min. 60 cm
Min. 60 cm
Min. 50 cm
Min. 60 cm
Min. 50 cm
0026_M_I
Min. 100 cm
Min. 60 cm
Fig. 2-9
Fig. 2-10