Caution for Ducting Work
●
This unit has high static pressure (applicable
external static pressure Max. 167~186 pa (17~19
mm Aq)).
In the case of small pressure resistance (for
instance short duct), install the damper for adjusting
air flow volume as air flow volume / air flow noise
increases.
●
If the air conditioner is to be installed in a room
such as an office or meeting room which needs a
low sound level, provide a supply and return noise
absorption chamber with an acoustic liner.
●
Include the air filter (field supply) at the return duct.