11
S4179544
(2)
When the branch tube after the distribution joint is connected
to only one indoor unit, it must have a trap. If not, when the
indoor unit is defective do not operate the system until the
defective unit is repaired. Otherwise the compressor may
develop problems because the refrigerant oil accumulates in
the branch tube.
1-10. Optional Distribution Joint Kits
●
APR-HV63MB1 : Cooling capacity after distribution is 16.0 kw (54,600 BTU/h) or less
●
APR-DV64MB
: Cooling capacity after distribution is 16.0 kw (54,600 BTU/h) or less
●
APR-DV94MB
: Cooling capacity after distribution is more than 16.0 kw (54,600 BTU/h)
Table 1-15
Distribution Branch Size (
lllll
1,
lllll
2,
lllll
3,
lllll
4)
Indoor Unit
9 type
12 type
18 type
25 type
36 type
48 type
Wide tube
12.7 (1/2)
15.88 (5/8)
19.05 (3/4)
Narrow tube
9.52 (3/8)*
NOTE
* For the 25 type, use the “Tube connector” (supplied with the unit) for sizing up a narrow tube
from 6.35 to 9.52.
Table 1-16
Dimensions of connections (shows the inner diameter of tubing)
Position
A
B
C
D
E
F
G
Size
ø28.58
ø25.4
ø19.05
ø15.88
ø12.7
ø9.52
ø6.35
Unit: mm
83
185
GF E
FG
E
E
F
G
0016_M_I
APR-HV63MB1
Wide tube
Narrow tube
103
210
E
E
D
E
D
D
C
C
C
0015_M_I
83
185
GF E
FG
E
E
F
G
0016_M_I
APR-DV64MB
Max. diameter
ø19.05
Min. diameter
ø12.7
Insulation
Wide tube
Max. diameter ø12.7
Min. diameter ø6.35
Insulation
Narrow tube
APR-DV94MB
Max. diameter ø28.58
Min. diameter ø19.05
(ø 12.7 —1)
142
300
Outlet
Inlet
Outlet
CB
A
A
BC
A
B
C
D
E
0017_M_I
Insulation
Wide tube
Max. diameter ø12.7
Min. diameter ø6.35
Insulation
Narrow tube
86
3/8"
3/8"
3/8"
3/8"
3/8"
324
60
100
60
60
0014_M_I
120
80
1/2"
1/2"
3/4"
140
374
60
60
60
1/2"
5/8"
0013_M_I
Unit: mm (in.)