3-36.
Removing and Attaching the Front Panel
(Floor-Standing Type).
A “dew-prevention heater” is secured behind the front
panel. When removing or attaching the panel, take
care not to damage the lead wire to the heater.
How to remove the front panel
(1)
Remove the two screws at the lower part of the
front panel.
(2)
Holding A at the upper right of the unit, push up at
B at the lower right of the panel. The right side of
the front panel is removed. Then remove the left
side of the front panel following the same
procedure.
(3)
Pull apart the lead wire connector (2P red) for the
dew-prevention heater
(4)
Remove the chain connecting the front panel of
the unit by unhooking it from the fixture attached
to the panel.
How to attach the front panel
(1)
Hook the chain to the fixture of the front panel
(2)
Connect the lead wire connector
(3)
Align the slots at the lower part of the front panel
to the tabs at the lower part of the indoor unit and
put the upper trim tab of the front panel on the
groove of the unit. Then press down the panel.
(4)
Insert the two screws at the lower part of the front
panel
3-37.
Installing the Refrigerant Tubing
(1)
When connecting the wide tube use the one
supplied.
(2)
Tubes can be extended in two directions,
downward and rear sides.
For floor standing type
●
When a rear-side tube is required, it can run
through the rear-tube outlet of the rear panel.
●
When a downward tube is required refer to the
opening dimensions shown in Fig. 3-109.
NOTE