CAUTION
(1)
When linking outdoor units in a network (S-
net link system), remove the short plug
(CN031, 2P Black, location: right bottom on
the outdoor control PCB) from all outdoor
units except any one of the outdoor units.
Otherwise the communication of S-net link
system does not perform.
For a system without link (no connection
wiring between outdoor units), do not remove
the short plug.
(2)
Do not install the inter-unit control wiring in a
loop. (Fig. 5-1)
Outdoor unit
Outdoor unit
Outdoor unit
0192_M_I
Prohibited
Prohibited
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Fig. 5-1
(3)
Don’t install the inter-unit control wiring such
as star branch wiring.
Star branch wiring causes mis-address
setting.
(4)
If branching the inter-unit control wiring, the
number of branch points should be 10 or less.
(Branches less than 1 m are not included in
the total branch number.) (Fig. 5-3)
Fig. 5-3
Outdoor unit
Indoor unit
Indoor unit
Indoor unit
0824_M_I
Indoor unit
Indoor unit
Indoor unit
Outdoor unit
Indoor unit
NG
NG
Branch point
Fig. 5-2
Outdoor unit
Outdoor unit
Outdoor unit
0193_M_I
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
more than 1 m
more than 1 m
Branch
point
10 or less
Indoor unit
Indoor unit
Indoor unit
Indoor unit
less than 1 m
Indoor unit