5.Parameter
[Parameter setting value【Group3】]
5−11
Page Contents
Position Loop Proportional Gain
3
[KP3]
10
Setting range
Unit
Standard value
1
〜
3000 1/s
30
Proportional gain for position controller.
Position Loop Integral Time Constant 3
[TPI3]
11
Setting range
Unit
Standard value
0.5
〜
1000.0 ms
1000.0
Integral time constant for position controller.
Integral term is disabled (proportional control) with the set
value of 1000.0ms.
✍
Cannot be used when position loop proportional
control switching function is enabled.
Velocity Loop Proportional Gain 3
[KVP3]
12
Setting range
Unit
Standard value
1
〜
2000 Hz
50
Proportional gain for velocity controller.
When load inertia is the one set by load inertia moment
ratio (load mass ratio) 2, the response is this set value.
Velocity Loop Integral Time Constant 3
[TVI3]
13
Setting range
Unit
Standard value
0.5
〜
1000.0 ms
20.0
Integral time constant for velocity controller. This setting is
enabled when velocity loop proportional control switching
function is disabled.
Integral term is disabled (proportional control) with the set
value of 1000.0ms.
Load Inertia Ratio (Load Mass Ratio) 3
[JRAT3]
14
Setting range
Unit
Standard value
0
〜
15000 %
100
Sets the inertia moment of load device to the motor inertia
moment. Set value
=
JL/JM
×
100%
JL
:
Load inertia moment
JM
:
Motor inertia moment
Torque Command Filter 3
[TCFIL3]
15
Setting range
Unit
Standard value
1
〜
2000 %
600
Parameter to set low pass filter to torque command. Sets
the cut off frequency.
Position Loop Proportional Gain 4
[KP4]
20
Setting range
Unit
Standard value
1
〜
3000 1/s
30
Proportional gain for position controller.
Position Loop Integral Time Constant 4
[TPI4]
21
Setting range
Unit
Standard value
0.5
〜
1000.0 ms
1000.0
Integral time constant for position controller. Integral term
is disabled (proportional control) with the set value of
1000.0ms.
✍
Cannot be used when position loop proportional
control switching function is enabled.
Velocity Loop Proportional Gain 4
[KVP4]
22
Setting range
Unit
Standard value
1
〜
2000 Hz
50
Proportional gain for velocity controller.
When load inertia is the one set by load inertia moment
ratio (load mass ratio) 2, the response is this set value.
Velocity Loop Integral Time Constant 4
[TVI4]
23
Setting range
Unit
Standard value
0.5
〜
1000.0 ms
20.0
Integral time constant for velocity controller. This setting is
enabled when velocity loop proportional control switching
function is disabled.
Integral term is disabled (proportional control) with the set
value of 1000.0ms.
Load Inertia Ratio (Load Mass Ratio) 4
[JRAT4]
24
Setting range
Unit
Standard value
0
〜
15000 %
100
Sets the inertia moment of load device to the motor inertia
moment. Set value
=
JL/JM
×
100%
JL
:
Load inertia moment
JM
:
Motor inertia moment
Torque Command Filter
4
[TCFIL4]
25
Setting range
Unit
Standard value
1
〜
2000 %
600
Parameter to set low pass filter to torque command. Sets
the cut off frequency.
Low Pass Filter of Gain Switching
[GCFIL]
30
Setting range
Unit
Standard value
0
〜
100 ms
0
Parameter to set time constant for gain switching.
The larger the value is, the gentler the switching is.
Содержание Q1AA04003D
Страница 3: ...TYPE S M0006890C Analogue Pulse Input Type Instruction Manual For Rotary Motor E N G L I S H ...
Страница 156: ...8 Maintenance Trouble Shooting 8 1 Alarm List 8 3 Trouble shooting when Alarm Occurs 8 5 Inspection Parts Overhaul 8 25 ...
Страница 238: ...Materials Dimension RS1 10 Materials 27 TION M TION M ...
Страница 239: ...Materials Dimension RS1 15 Materials 28 M TION TION M ...
Страница 240: ...Materials Dimension RS1 30 Materials 29 TION M TION M ...
Страница 256: ...Materials Option Metal mounting fittings Materials 45 AL 00582789 01 AL 00582791 01 ...
Страница 257: ...Materials Option Metal mounting fittings Materials 46 AL 00582790 01 AL 00582792 01 ...