SEC1000 FIRE ALARM CONTROL PANEL
Page
13
of 24
5.2.2 Bus setup
All configurations and commissioning relating to the bus is set under the BUS category,
including naming of zones, registering and assignment of detectors/modules, and reading of
the system details. The sub-menus are as example below:
Zone setup
When this menu option is selected, a window is shown to allow you to register and add a
description for a specific zone, and to configure the ‘Resound’ option.
Note
: When using the panel networking function, in order to avoid displaying confusion or
communication error, try to configure and register different zones on different networking panels.
Detector/module setup
All detectors and modules in the system can be configured under this setup window by
completing the corresponding options.
Tick the ‘Reg’ will register and assign the device to the loop with a unique ‘Address’ number.
The following is the setup for the Product Type of a detector:
The ‘Resound’ function is selected to
determine whether the silenced sounder(s)
of all zones will resound automatically on a
new fire signal from any other zone. This
function only applies to loop sounders,
excluding sounders on the S.C.Out circuit.