SEC1000 FIRE ALARM CONTROL PANEL

Page

13

of 24

5.2.2 Bus setup
All configurations and commissioning relating to the bus is set under the BUS category,
including naming of zones, registering and assignment of detectors/modules, and reading of
the system details. The sub-menus are as example below:

Zone setup

When this menu option is selected, a window is shown to allow you to register and add a
description for a specific zone, and to configure the ‘Resound’ option.

Note

: When using the panel networking function, in order to avoid displaying confusion or

communication error, try to configure and register different zones on different networking panels.

Detector/module setup

All detectors and modules in the system can be configured under this setup window by
completing the corresponding options.

Tick the ‘Reg’ will register and assign the device to the loop with a unique ‘Address’ number.
The following is the setup for the Product Type of a detector:

The ‘Resound’ function is selected to
determine whether the silenced sounder(s)
of all zones will resound automatically on a
new fire signal from any other zone. This
function only applies to loop sounders,
excluding sounders on the S.C.Out circuit.

Содержание SEC1000

Страница 1: ......

Страница 2: ...imum loop cable length recommendations 8 3 8 Other terminal connections 8 4 Indications and Controls 9 4 1 LED indicators 9 4 2 Button controls 10 4 3 Zone Indicators 11 5 Commissioning and Programmin...

Страница 3: ...loop of 120 addressable points and expansion capabilities It is compatible with other peripherals made by Sanjiang with its own protocol 2 2 Technical Specifications Power supply Mains supply 230VAC...

Страница 4: ...n rate 9600 bps Recommended type of cable Unscreened twisted pair 1mm2 Transmission distance 1000m Cable diameter 1mm2 2 5mm2 CAN Max number of panels 20 Transmission rate Optional 10K 20K 50K and 100...

Страница 5: ...refer to the separate manual of PMC_01 and the datasheet of Switching Power Supply for more details The P S E is an integrated unit that provides power both for the panel and the backup rechargeable...

Страница 6: ...C1000_COM PMC_01 LSP 75 24 ADJ TB4 LED TB3 DC TB2 AC TB1 AC TB5 Red Black Red Red Black Red Red Black Black Red Black Yellow green Blue Brown RS485 3 3 Mounting the chassis to the wall The panel can b...

Страница 7: ...0V 10A L N Red Black Red Black Red Red Black Black Yellow green Blue Brown To Battery 3 5 Battery connection For this single loop system 2 12V 7Ah sealed lead acid batteries are used as per the calcul...

Страница 8: ...Loop In and Loop Out terminal block on the MB Board It should be noted when the loop is in class B connection the terminal LOOP INPUT on MB Board is not available Means to limit the consequences of sh...

Страница 9: ...meter Typical Resistance 1 0mm2 18 1 ohm km 1 5mm2 12 1 ohm km 2 5mm2 7 41 ohm km 3 8 Other terminal connections 1 F A Out short for Fire Alarm Output When there is a general fire the output is activa...

Страница 10: ...d POWER FAULT Lit yellow when the panel s mains power battery or charger is in fault condition SYSTEM FAULT Lit yellow when the panel is unable to provide mandatory functions POWER Lit green to show t...

Страница 11: ...access level 2 3 Press again to resound the sounders previously silenced Silences the panel s internal buzzer COPY Copies the content of text selected currently PASTE Pastes the content of text copie...

Страница 12: ...ompletion of all the installation and connection work It includes registering and test of detectors and modules setup of the zone indication and control panel C E programming and etc All these functio...

Страница 13: ...ion rate The number of each panel should be different There are 4 transmission rates 10K 20K 50K 100K Some factors like the total number of network panels the transmission distance of the system and t...

Страница 14: ...ing function in order to avoid displaying confusion or communication error try to configure and register different zones on different networking panels Detector module setup All detectors and modules...

Страница 15: ...ct Type are kept the same as detectors Refer to the Annex device type list for all the Device Type provided in this system The Zone refers to where a device belongs in the protected premises It repres...

Страница 16: ...g In the event of a fire a default output of sounders will be activated Besides this outputs of specified modules can be set here as per requirements from the client specifier Click by the USB mouse o...

Страница 17: ...e For the function of overriding delays by activating any MCP in the system it refers to the delay which is running If the MCP used to override the delays is involved in another c e rule with a time d...

Страница 18: ...hey are point test module start stop and duplicate address check Check duplicate address This function helps you to locate detector module with duplicate addresses on the loop When Check clicked it st...

Страница 19: ...prompts below the loop learn process may take about 120s and it cannot be stopped during the period When the auto learn completes successfully a comparison between the loop learn result and the initi...

Страница 20: ...ata backup Take the prompt as reference Load data from U disk This function will load the configuration file from U disk to the panel s flash and overwrite the panel s existing data So this function m...

Страница 21: ...rating as the prompt says will complete 5 2 6 View system and software version info The system information as well as the version of each processor with program can be read through the corresponding m...

Страница 22: ...tor or a manual call point is typically 0 001A or 1mA while that of a input output modules or Intelligent Sounder Beacon is 0 008A or 8mA IRout is the alarm output current of the panel s three relays...

Страница 23: ...son and solution check if the connector to the terminal of Loop Out or Loop In is loose Check if the circuit between Loop Out and Loop In exists an interruption Problem a fault of loop short is report...

Страница 24: ...int MCP Fire Hydrant Call Point HydrCP Sounder Visual Indicator Sounder Strobe SoundStro Sounder Sounder Visual Alarm Strobe Strobe Alarm Bell Alarmbell Conventional Optical Detector ConvOptD Conventi...

Страница 25: ...DelugeVal Generator Generator Stabilized Pressure Pump PressPump Fire Pump FirePump Foam Pump FoamPump Water Pump WaterPump Air Conditioner Air con Fire Emergence Evacuation Broadcast BCST Fire Emerg...

Страница 26: ...SEC1000 FIRE ALARM CONTROL PANEL...

Отзывы: