SEC1000 FIRE ALARM CONTROL PANEL
Page
2
of 24
1. About This Manual
This manual contains information necessary for the use of personnel engaged in the
installation and commissioning of the SEC1000 Fire Alarm Control Panel, regarding the
connection of the panel with its peripherals, programming of all the functions, etc.
This document does not cover panel operation or functionality. This data can be found in the
separate Operating Manual.
2. Introduction
2.1 Overview
The purpose of the SEC1000 Fire Alarm Control Panel (FACP) is to monitor input signals, give
indications and possibly activate outputs as programmed. It is designed to comply with EN
54-2 with qualities of simple installation, operation and easy maintenance.
The SEC1000 panel is an addressable fire detection panel with 1 loop of 120 addressable
points and expansion capabilities. It is compatible with other peripherals made by Sanjiang
with its own protocol.
2.2 Technical Specifications
Power supply
Mains supply
230VAC (-15%, +10%). 47 ~ 63Hz. Max current 0.85A
Mains fuse
T3.15AL250V
Operating voltage
20 ~ 28VDC
Recommended mains cable
Standard/black mains cable, cable size 0.75mm
2
Power rating
Imin=0.45A; Imax.a=1.15A; Imax.b=1.65A
Max. battery supply current
3A (when the Mains is disconnected)
Max. charging current
1A
Battery capacity, type and
recommended model
NP7-12 for 7Ah VRLA(Yuasa)
Max. internal resistance of battery
1Ω
Battery fuse
F6AL250V
Quiescent current (full loaded)
< 0.4A
Outputs
S.C.Out (+, -)
Output voltage
20 ~ 28VDC
Max. output current
800mA, 1A S.C.Out+24VK in total
End of line resistor
47K ohm 0.25W
Recommended type of cable
Plain unscreened cable, 1.5mm
2
Cable diameter
1mm
2
~ 2.5mm
2
Transmission distance
≤1500m
F.A. Out (+, -)
Output voltage
20 ~ 28VDC
Max. output current
100mA
End of line resistor
47K ohm 0.25W