SEC1000 FIRE ALARM CONTROL PANEL
Page
14
of 24
Since the Product Type is an inherent attribute of a field device, the optional product types
provided in this system are listed as follows.
Ionization detector
Optical detector
Heat detector
Strobe
Infrared detector
Combination detector JS input module
Gas detector
JK input module
Output module
Input/output module I/O module-Broadcast
KZJ_LD module
Manual control button Manual call point
Fire indicating panel
Fire hydrant call point
Sounder strobe
Sounder
The following figure shows the setup for the Device Type of an output module:
The Device Type is a concept specially defined for module devices, which refers to the type of
device a module connects with. For example, the Device Type of an output module could be
fire door, blow valve, etc.
Therefore for detectors, the Device Type and Product Type are generally the same. For
modules, the Device Type and Product Type are usually different, except for the six special
modules of manual control button, manual call point, fire hydrant call point, sounder strobe,
sounder and strobe whose Device Type and Product Type are kept the same as detectors.
Refer to the Annex (device type list) for all the Device Type provided in this system.
The Zone refers to where a device belongs in the protected premises. It represents a detection
zone for detector or manual call point, while representing an alarm zone for sounders. Except
detector, MCP and sounder, it only indicates the geographical area the device is mapped to.
Note
: When it comes to the function of disabling a zone, or the indication of a zone in a functional
condition, it exclusively means a detection zone. For the default c&e function (see section 5.2.3), we
consider the detection zone as the same area of the alarm zone with the same zone number.
The Output Mode refers to the control mode of an output type module when transmitting
signal to its following device. Thus, this option is ineffective to detectors or input type module.
When Pulse is chosen, the output driver signal of the module will cut off after 5-10s. When
Constant is chosen, the driver signal exists continuously. Constant is commonly set.
There are three Work Modes for detectors: Normal, Fast and Slow. It is recommended to use
the Fast mode since Normal and Slow modes are adopted under some special applications.
Here, the device following the
output module of address no.1
is an electromagnetic valve.