SEC1000 FIRE ALARM CONTROL PANEL
Page
15
of 24
Batch setup
If several devices with consecutive addresses have same features to be set, an alternative to
configuring them all individually is to make a batch set. Double-click the option title to be set
or press direction buttons to select one column and press ENTER, the setup window then
pops up. Take the column of ‘Zone’ as an example:
Bus setup
The bus type of the Loop can be selected under this setup window, Class A or Class B. The
default setup is Class A.
5.2.3 C&E programming
In the event of a fire, a default output of sounders will be activated. Besides this, outputs of
specified modules can be set here as per requirements from the client/specifier.
Click by the USB mouse or press
►
to select the C&E menu option. It shows 5 sub-menus:
Default c&e
A default output is designed for the sake of c&e setting brevity, that is, the associated zonal
sounder will be activated when a fire occurs. Meanwhile, the default output to the loop
sounders can be delayed by a time of 5s, 10s, 30s, 60s, 90s, 120s or 150s.
As the figure shows left, a range of
addresses can be specified so that the
devices involved are all assigned to
zone 3.
Note: When the loop is in class B , the
terminal LOOP INPUT on MB-Board is
not available.