38 S&C Instruction Sheet 1074-530
SpeedNet Client Tool
IP Routing Window,
Routes Tab
Figure 58. Routes IP routing configuration window.
The
Routes
tab, shown in Figure 58, is used to view or delete existing data communica-
tion route table entries, and to add new route table entries. The following parameters can
be configured:
•
Route Table
—The Route Table parameter displays a list of current routes within the
SpeedNet ME Radio route table. If mesh networking is used, the route table entries
will be updated dynamically to reflect changes to the network.
•
Add Route
—The
Add Route
button is used to add static routes to the route table and
is described below.
•
Add Default
—The
Add Default
button is used to add a static default gateway to the
route table and is described below.
•
Delete
—To delete a route from the route table, first select the route. Then click the
Delete button to remove the route from the route table.
Adding Static Routes
Clicking the
Add Route
button will add an Add Route section to the
Routing
tab. See
Figure 59.
Figure 59. Add Route settings.
•
Network
—This is the destination network for the route that is being created. To
enter a static route for a device with an address of 192.168.200.1 and a subnet mask of
255.255.255.0, the Network portion of the route entry should be 192.168.200.0.
•
Subnet Mask
— This is the subnet mask for the destination network for which the
route is being created.
•
Gateway
— This is the next-hop gateway of the destination network for which the
route is being created. The gateway will be the IP address of the wireless interface of
a SpeedNet ME Radio.
•
Add
—After entering the details of the static route, click the
Add
button to add the
route to the route table.
•
Cancel
—Click the
Cancel
button to cancel the route creation process.