26
S&C Instruction Sheet 1041-550
IntelliLINK
Bite
First IIN Byte Definition
Second IIN Byte Definition
0
Broadcast message received
Function code not implemented
1
Class 1 data available
Requested object unknown
2
Class 2 data available
Parameters in the qualifier, range, or data
fields are not valid or out of range
3
Class 3 data available
Event or application buffers have over-
flowed
4
Time-synchronization required
from master
Requested operation is already executing
5
Control is in local mode
Configuration corrupt
6
Device trouble
Reserved
7
Device restart
Reserved
Figure 11. TROUBLESHOOTING: Communications screen (PG&E SCADA version).
The log can hold 10 entries. Once the log is full, each new event over-writes the oldest
event in the log. To find the most recent event, look for the message with a timestamp that
is older than the time for the message above it.
TABLE 1. DNP Internal Indication Bits Status Field Codes.