2

    S&C Instruction Sheet 1041-550 

Introduction

Qualified Persons

Read this 
Instruction Sheet

Retain this 
Instruction Sheet

Warranty

Ç

 WARNING

The equipment covered by this publication must be installed, operated, and main-
tained by qualified persons who are knowledgeable in the installation, operation, 
and maintenance of overhead electric power distribution equipment along with the 
associated hazards.

  A qualified person is one who is trained and competent in:

•   The skills and techniques necessary to distinguish exposed live parts from non-

live parts of electrical equipment.

•   The skills and techniques necessary to determine the proper approach distances 

corresponding to the voltages to which the qualifi ed person will be exposed.

•   The proper use of the special  precautionary  techniques,  personal  protective 

equipment, insulating and shielding materials, and insulated tools for working on 
or near exposed energized parts of electrical equipment.

These instructions are intended only for such qualified persons. They are not 

intended to be a substitute for adequate training and experience in safety procedures 
for this type of equipment.

Thoroughly and carefully read this instruction sheet before programming, operating, or 
maintaining your S&C 5800 Series Automatic Switch Control. Familiarize yourself with the 
safety information on page 3. The latest version of this instruction sheet is available online 
in PDF format at www.sandc.com. Select: Support/Product Literature Library.

This instruction sheet is a permanent part of your S&C 5800 Series Automatic Switch Control. 
Designate a location where you can easily retrieve and refer to this publication. 

The standard warranty contained in S&C’s standard conditions of sale, as set forth in Price Sheets 
150 and 181, applies to the S&C 5800 Series Controls, except that the first paragraph of said 
warranty is replaced by the following:

 (1)

 

General:

 Seller warrants to immediate purchaser or end user for a period of 

10 years from the date of shipment that the equipment delivered will be of the kind and 
quality specified in the contract description and will be free of defects of workmanship and 
material. Should any failure to conform to this warranty appear under proper and normal 
use within ten years after the date of shipment the seller agrees, upon prompt notification 
thereof and confirmation that the equipment has been stored, installed, operated, inspected, 
and maintained in accordance with recommendations of the seller and standard industry 
practice, to correct the nonconformity either by repairing any damaged or defective parts 
of the equipment or (at seller’s option) by shipment of necessary replacement parts. The 
seller’s warranty does not apply to any equipment that has been disassembled, repaired, 
or altered by anyone other than the seller. This limited warranty is granted only to the 
immediate purchaser or, if the equipment is purchased by a third party for installation in 
third-party equipment, the end user of the equipment. The seller’s duty to perform under 
any warranty may be delayed, at the seller’s sole option, until the seller has been paid in 
full for all goods purchased by the immediate purchaser. No such delay shall extend the 
warranty period.

  Replacement parts provided by seller or repairs performed by seller under the warranty 
for the original equipment will be covered by the above special warranty provision for its 
duration. Replacement parts purchased separately will be covered by the above special 
warranty provision.

  Warranty of S&C 5800 Series Automatic Switch Controls is contingent upon the installa-
tion, configuration, and use of the control or software in accordance with S&C’s applicable 
instruction sheets. 

  This warranty does not apply to major components not of S&C manufacture, such as 
batteries, and communication devices. However, S&C will assign to immediate purchaser 
or end user all manufacturer’s warranties that apply to such major components.

Содержание 5800 Series

Страница 1: ...afety Instructions 3 Replacement Instructions and Labels 3 IntelliLINK Software Applicable Software 4 Troubleshooting Overview 5 Power Problems 6 LCD Problems 6 Software Troubleshooting and Error Mess...

Страница 2: ...g 1 General Seller warrants to immediate purchaser or end user for a period of 10 years from the date of shipment that the equipment delivered will be of the kind and quality specified in the contract...

Страница 3: ...roduct or property damage if instructions including recommended precautions are not followed NOTICE NOTICE identifies important procedures or requirements that can result in product or property damage...

Страница 4: ...safety procedures when working on or around this switch control Before attempting to access an existing switch installation check carefully for visible or audible signs of electrical or physical malfu...

Страница 5: ...lems on page 15 To view these screens you need a portable IBM PC compatible computer a serial cable and the IntelliLINK version for this 5800 Series switch control For more informa tion about the equi...

Страница 6: ...D module may need to be replaced Backlighting on the LCD does not light Do a lamp test Hold the faceplate BATTERY TEST LAMP TEST switch in the LAMP TEST position If the backlighting does not come on b...

Страница 7: ...ide test point check for voltage at the fuse side test point See Figure 2 e With all power sources disconnected tighten the screws behind the AC LINE fuse Disconnect the ac power line and the battery...

Страница 8: ...ED is always off when ac power is off For sensor powered controls check PS IO J8 For sensor powered controls check the voltage from the sensors d Check the battery voltage Disconnect the battery With...

Страница 9: ...ller Data File dialog box select the snapshot you want to view then click OK to open both the snapshot and the correct screenset IntelliLINK setup incorrect or incomplete Reinstall the IntelliLINK sof...

Страница 10: ...a problem with one of the files For details see To Install the IntelliLINK Software in the Setup Instruction Sheet 1041 530 Times New Roman font is not on your system The project requires it Click OK...

Страница 11: ...y powered controls check the power line Following utility approved work procedures and safety practices verify that the distribution circuit is energized and that load current is flowing through the s...

Страница 12: ...was logged Check the OVERCURRENT FAULT Fault Events screen to see whether the switch control detected and took action on the fault If it logged the fault go to Step B If not go to Step C b Check when...

Страница 13: ...ails b Check the faceplate REMOTE LOCAL switch Toggle the faceplate REMOTE LOCAL switch to REMOTE c Check the RTU address At the SETUP Communications screen check which Communications RTU Address is u...

Страница 14: ...access it from any other screen click the Operation button Figure 3 OPERATION screen S C 5801 shown The upper part of the screen reflects the status of the LEDs on the faceplate For a full descriptio...

Страница 15: ...is open and the faceplate is receiving power this field displays the message Door Open For switch control malfunctions that can also cause this message see Cabinet Door on Operation screen shows wrong...

Страница 16: ...shooting Event Status screen page 1 5801 shown This screen contains 5 columns no title The name of the event Status If the status of an event is Active it means that the condition presently exists Cou...

Страница 17: ...SABLE switch is in the ENABLE position A Stop Transfer condition will exist if auto matic operation is disabled Tamper Switch Door Open This field displays an Active message when the switch control en...

Страница 18: ...line switch NOTE For S C 5802 5803 controls the Switch Not Ready Conditions are on page 3 of the TROUBLESHOOTING Event Status screen To display these fields click the PgDn button at page 2 of the scr...

Страница 19: ...us Hot Line Tag may only be set if the following conditions are true The switch must be Open Switch contacts must be consistent No switch operation is pending If any of these three conditions are not...

Страница 20: ...ological Log screen The log can hold three pages of information Once the log is full each new event over writes the oldest event in the log To find the most recent event look for the message with a ti...

Страница 21: ...Control software this field includes the message Unrecognized superseded If the IntelliLINK version is newer than the Control software this field includes the message Not Current Release If you try t...

Страница 22: ...ns that begin with a SCADA or faceplate close command while the switch is in a valid open position and end with a closed signal from the switch s status circuits The switch control filters out excess...

Страница 23: ...on This is the line switch operation that occurred and the source of the command to change the switch position Open The switch opened Close The switch closed Faceplate Operation The command came from...

Страница 24: ...es DNP protocol see Figure 9 below If your switch control uses PG E SCADA Cooper 2179 protocol see Figure 10 on page 25 Figure 9 TROUBLESHOOTING Communications screen DNP version The log can hold 10 e...

Страница 25: ...ived Invalid index size received Invalid qualifier code received Invalid object range received Invalid object header parameters Control is in local mode Message received with broadcast address Timer s...

Страница 26: ...n buffers have over flowed 4 Time synchronization required from master Requested operation is already executing 5 Control is in local mode Configuration corrupt 6 Device trouble Reserved 7 Device rest...

Страница 27: ...Control selection followed by non operate Unsupported ordinal read write request Ordinal read from write to invalid memory Scan request contains bad sequence number Scan by table request w bad table n...

Страница 28: ...cannot be recovered b Click on Clear All in the upper right corner of the screen This causes all counters and statistics to return to 0 except the Min 2way which clears to the maximum value of 255 Th...

Страница 29: ...e received due to a busy receive channel Xmt Busy This field shows the number of times a packet was unable to be transmitted due to a busy transmit channel These are errors associated with the applica...

Страница 30: ...d requests if it is waiting to receive confirmation from the master station for an outstanding eventdata response message Other Err This field shows the number of unidentified errors encountered These...

Страница 31: ...e following fields Battery Voltage Low Setpoint Volts DC When the battery voltage is between this value and the Battery Bad value switch operation is still possible but only for a limited time When th...

Страница 32: ...icates the type of charger malfunction The field is set or cleared during a battery test Three states are possible N A Not applicable no alarms are present Overvoltage Ahighvoltagewasappliedtobatterys...

Страница 33: ...pically has an impedance of 0 125 0 150 ohms Predicted Minimum Voltage Under Load This is the voltage that the switch control estimates will be present at the battery terminals when the switch is oper...

Страница 34: ...Printed in U S A...