S&C Instruction Sheet 1041-550
19
Low Pressure (if appl.) (Vista switches)
If applicable, this field displays an
Active
message when the switch control detects low
pressure inside a switch (operator) equipped with low pressure sensing.
Switch 1 in Local Mode (PME and PMH switches)
Switch 2 in Local Mode (PME and PMH switches)
Switch 3 in Local Mode (PME and PMH switches)
This field displays an
Active
message when the external
REMOTE/LOCAL
switch on this
pad-mounted switch, located in the PM Operator compartment, is set to
LOCAL
.
Switchgear in Local Mode (Vista switches)
This field displays an
Active
message when the external
REMOTE/LOCAL
switch on this
switchgear is set to
LOCAL
.
Position 1 Grounded (Vista switches)
Position 2 Grounded (Vista switches)
This field displays an
Active
message when this switch has been opened and put in the
grounded position.
Hot Line Tag
The Hot Line Tag feature modifies the automatic and manual operation of the switch and
prevents the control from closing the switch when it is applied.
Hot Line Tag can only be
Set
and
Cleared
with a SCADA command.
Latch On
sets Hot
Line Tag, and
Latch Off
clears Hot Line Tag. A binary Status Point communicates the
Hot Line Tag state, where a value of 1 indicates
Active
status, and a value of 0 indicates
Inactive
status.
Hot Line Tag may only be set if the following conditions are true:
•
The switch must be
Open
,
•
Switch contacts must be consistent,
•
No switch operation is pending.
If any of these three conditions are not met, the control will return a hardware error 1
response to the SCADA command to set Hot Line Tag, and the tag will remain
Cleared
.
Whe Hot Line Tag is set or active the Scada-Mate® Switch is inhibited from
Closing
by
all means:
•
Locally by a front-panel command,
•
Locally via directly-connected IntelliLINK® software,
•
Remotely via IntelliLINK Remote Software,
•
Remotely by a SCADA command.
The sole exception to the
Close
inhibit is the local operating mechanism (hotstick opera-
tion) on the Scada-Mate Switch. The 5801 embedded control software is locally overridden
by the operating mechanism. Such operation will not result in the tag being cleared, and
the control will still be inhibited from performing any
Close
operations.
Hot Line Tag status is displayed in the
Maintenance
category of the LCD display.
When Hot Line Tag is set, the tag status will be displayed with the message:
Caution: Hot
Line Tag Applied
. As long as the Hot Line Tag remains active, LCD data scrolling will be
disabled and only the Hot Line Tag status message will be displayed. When the Hot Line
Tag is inactive, confirmation of this status will be provided by scrolling the LCD data dis-
play to the
Hot Line Tag
status under the
Maintenance
category, which will display the
message:
Hot Line Tag Cleared
.
IntelliLINK