13-3.Cab Mode
This mode is appeared as pressing "SET" key for 5 sec or more and is disappeared as pressing
"SET" key shortly once more,
a
lso it is not recommened that user makes a calibration without
checking by accurate source
ㅋ
Function/range
Description
Factory setting
value
P0000
Password Input
*need to input factory value "0000" to enter
into this mode group
*to calibrate slight difference between
indication and actual value ,-12.7%
*next mode by pressing right direction key
"CLR"
0000
CrPEr
to have a
caribration for
phase "R" current
*possible to adjust , - 12.7% from
indicated value by using "UP" or "DN" key
0
CsPEr
to have a
caribration for
phase "S" current
0
CtPEr
to have a
caribration for
phase "T" current
0
vrPEr
to have a
caribration for
phase "R" voltage
0
vsPEr
to have a
caribration for
phase "S" voltage
0
vtPEr
to have a
caribration for
phase "T" voltage
0
EcPEr
to have a
caribration for
ground fault current
tEPEr
to have a
caribration for
temperature
tranS/OFF/
d-Ear
to select indication
pattern of
incomming voltage
*OFF: to indicate line voltage:v1,v2,v3
*d-Ear:to indicate average voltage
OFF
PEdIt/setting
Value(P****)
to change password
*possible to enter new digit by using "UP" or
"DN" key after positioning a curser on the
required digit
*possible to enter into main mode or sub
mode as pressing "mode" key
vUb/OFF/
setting value
to preset voltage
unbalance
protection rate(%)
*trip in case preset rate condition is kept on
preset time or more
*rate:[(Max V-Min V)/Max V]*100 [%]
*adjustable range:2%~40%
OFF
v-uT/
setting value
to preset operating
trip delay time for
voltage unbalance
*to preset a operating trip time for voltage
unbalance
*Adjustable range: 0.5~10 sec
3
Содержание DSP-VIP-PL
Страница 1: ...Voltage Current based Digital Multi function Motor Protection Relay DSP VIP PL PM...
Страница 2: ......
Страница 10: ...Acceptable with both rating of ZCT High Level Protetion Class...
Страница 12: ...Note The detail about MWR S 485 recorder is described in the manual for MWR S Various and Multiple Indication...
Страница 37: ...15 5 2 Level Higher Level Lower Level Alarm to Over Current 15 6 SC F MC R Transit time 0 2 sec...
Страница 45: ...19 3 Y D Start 19 4 Foward Reverse Start...
Страница 46: ...19 5 Reactor start 20 Rotated Indication 20 1 Basic factor V I KW GR...
Страница 51: ...21 3 Center PC PLC DSP by RS 485 422 through Gateway...
Страница 56: ...23 Dimension Converter Communication Module Converter Loader Display Meter Loader...