25. Guide for user
This product should be maintained by qualified engineer according to manufacturer's
guide, so a damage or something wrong of this product which comes from vioiolating this
guide may cost to user
Using environment is as follows:
1)Temperature:-25 OC ~+70 OC
2)Storage :-40 OC ~ +80 OC
3)Humidity:30 ~ 80%/RH,Non-condensing
4)Voltage
The control voltage is AC 85V~260V , 50/60Hz( DC 90V~370V) or AC/DC 24V and
allowable deviation for this voltage is +.-10% .
1)a supplied voltage greater than rating value many be given a damage to incoming
part of DSP,so customer must keep allowable deviation of input voltage.
Also this control voltage must be supplied through a transformer insulated between
primary and secondary,also proper fuse/do not use Line-Neutral Voltage in 3P4W
2)in case of the interface between Note PC and DSP directly by RS232 to monitor and
to preset data ,power source for Note PC also must be provided through an
insulated transformer and a proper fuse above mentioned,otherwise RS 232
communication could be interfered
3)fastening screw:a connection between a terminal of DSP and a wire must be done
clearly and surely, but user should be care of distortion caused by extra fastening
torque
4)It is not possible that an operator presets a data directly DSP and a motor are working ,
so if user wants to do so,please stop to operate a motor.
An operator should not combine a converter with a loader and a display meter while
the motor is working,s o if necessary to do so, a motor should be stopped.
An operator should not control DIP SW while a motor is working. If necessary to do
so, a motor should be stopped and be done in waiting mode state
Operator need to use RS 422/485<>RS232(USB) protocol converter,so USB must have
isolated power to connect communication module of DSP-VIP to PC in serial
connection . This converter is one of common accessory provided by other manufacturer.
The more detailed information about a communicatio between PC and VIP is also
described in the manual for a communication module
Содержание DSP-VIP-PL
Страница 1: ...Voltage Current based Digital Multi function Motor Protection Relay DSP VIP PL PM...
Страница 2: ......
Страница 10: ...Acceptable with both rating of ZCT High Level Protetion Class...
Страница 12: ...Note The detail about MWR S 485 recorder is described in the manual for MWR S Various and Multiple Indication...
Страница 37: ...15 5 2 Level Higher Level Lower Level Alarm to Over Current 15 6 SC F MC R Transit time 0 2 sec...
Страница 45: ...19 3 Y D Start 19 4 Foward Reverse Start...
Страница 46: ...19 5 Reactor start 20 Rotated Indication 20 1 Basic factor V I KW GR...
Страница 51: ...21 3 Center PC PLC DSP by RS 485 422 through Gateway...
Страница 56: ...23 Dimension Converter Communication Module Converter Loader Display Meter Loader...