OV/UV
1a,Normal
de-energized
*In case "voltage" is selected
in Line Mode
.Over Voltage Trip
.Under Voltage Trip
.Voltage Unbalance
*In case "OFF" is selected in
Line Mode
-Lower alarm level(ALLc)
to OC,30%~ under Alhc
level
-Contact is closed after 3
sec under preset alarm
level,but main trip relay is
not trip.
-Only trip cause is appeared
in display window in the
position of voltage factor on
the way of continued
display rotation ,in case
this trip output is energized
during a motor runs.
*In case both OP & UP
mode is OFF in the same
time, then "SS" trip output
comes out through this
output
13.Preset Description
13-1.Main Mode
Mode
Function/range
Description
Factory Setting
value
P0000
Password
*Press "SET" button to have a preset.
*Input a factory setting number,"0000" to enter
setting mode
*Move a cursor from first digit(1000 unit) to last
digit(1 unit) to pass over next mode as pushing
CLR key(Enter function) 4 times.
*possible to change password made by "PEdIt"
mode in CAB mode group
*If the operator forget a password,
manufacturer can support it or use a procedure to
call factory initialized setting value
*To call factory seting value,make pressed state
for Test button of converter at first under power-
off condition, then power-on under pressed state of
test button for 3 sec or more
0000
Содержание DSP-VIP-PL
Страница 1: ...Voltage Current based Digital Multi function Motor Protection Relay DSP VIP PL PM...
Страница 2: ......
Страница 10: ...Acceptable with both rating of ZCT High Level Protetion Class...
Страница 12: ...Note The detail about MWR S 485 recorder is described in the manual for MWR S Various and Multiple Indication...
Страница 37: ...15 5 2 Level Higher Level Lower Level Alarm to Over Current 15 6 SC F MC R Transit time 0 2 sec...
Страница 45: ...19 3 Y D Start 19 4 Foward Reverse Start...
Страница 46: ...19 5 Reactor start 20 Rotated Indication 20 1 Basic factor V I KW GR...
Страница 51: ...21 3 Center PC PLC DSP by RS 485 422 through Gateway...
Страница 56: ...23 Dimension Converter Communication Module Converter Loader Display Meter Loader...