Ground Fault
Trip is done if a current
greater than preset zero
phase current is kept for
Eot(earth operating time)
*according to selection of DIP SW:ZCT
rating is used for 200mA/1.5mA or
200mA/100mV
Over
temperature
*Trip is done if the
temperature sensed by
PT100 greater than preset
temperature is kept over 8
sec
* If sensed temperature is
greater than preset value,
motor can not start
Phase Loss by
line voltage
*This protection is identified
by line voltage
*Trip time is within 0.5 sec.
*"OFF" is possible in this
mode
*If each of 3 phase is a state of phase loss
in the same time,which means normal
"power off", this mode does not response
to such state
*If phase loss is happened, auto reset is
not possible,but manual reset.
Phase Loss by
load current
*This protection is identified
by load current
*Trip time:1~5 sec/definite.
*"OFF" is possible in this
mode
*If phase loss is happened,auto reset is
not possible,but manual reset.
Reverse Phase by
line voltage
*This protection is identified
by line voltage
*Trip time is within 0.5 sec.
*"OFF" is possible in this
mode
*If reverse phase is happened ,auto reset
is not possible ,but manual reset.
Reverse Phase by
load current
*This protection is identified
by load current
*Trip time is within 0.5 sec.
*"OFF" is possible in this
mode
*If reverse phase is happened, auto reset
is not possible,but manual reset.
8. Indication List
Item
Description
Remarks
Line Voltage
Incoming Line/V1,V2,V3 or Average
voltage(selected in "trans" mode of
"cab" mode group)
*110V is based on a
secondary voltage of PT
*In case incoming voltage is
zero in the same time:OFF
is shown
Load Current
L1,L2,L3
Temperature/cas
e,winding
1
O
C ~ 150
O
C/scale 1
O
C
Power factor
COS Phi
In case of 110V, it is based
on secondary voltage of PT
for correct calculation
Содержание DSP-VIP-PL
Страница 1: ...Voltage Current based Digital Multi function Motor Protection Relay DSP VIP PL PM...
Страница 2: ......
Страница 10: ...Acceptable with both rating of ZCT High Level Protetion Class...
Страница 12: ...Note The detail about MWR S 485 recorder is described in the manual for MWR S Various and Multiple Indication...
Страница 37: ...15 5 2 Level Higher Level Lower Level Alarm to Over Current 15 6 SC F MC R Transit time 0 2 sec...
Страница 45: ...19 3 Y D Start 19 4 Foward Reverse Start...
Страница 46: ...19 5 Reactor start 20 Rotated Indication 20 1 Basic factor V I KW GR...
Страница 51: ...21 3 Center PC PLC DSP by RS 485 422 through Gateway...
Страница 56: ...23 Dimension Converter Communication Module Converter Loader Display Meter Loader...