→ Panel Mounting Type : Loader 

 

 

12.Trip Relay Output 

 

Trip 

Relay 

Output 

Remark 

Main   

C1-SC/F-
MC/R :1a X 3 

*Over Load/OverCurrent 

Output for short 
protecction comes out 
through main trip or Aux 
trip 

*Under Load/Under Current 

*Locked Rotor 

*Phase Loss 

*Reverse Phase 

*Ground Fault 

*Over Temperature 

*Current Unbalance 

*Shock 

*Short 

Aux   

1a,Normal   
de-energized 

*Selected in Au-o mode(one of 
OFF, Ec , uc ,Shoc, Al,tEP, 
Ec-tE, SS-tr,Ec-ta,Ec-tb 
*OFF:same as Main Trip 
*SS-tr: trip caused by short 
circuit same as main trip 
*Main Trip(it means motor is 
stopped like a case of main 
trip diffrenent from alarm) 
*Ec-ta,Ec-tb:Main trip action 
caused by Ec dependent   
from main trip   
    .Ec-ta:normal energized   

state(open

close) 

    .Ec-tb:normal de-energized   

  state(open

open) 

*Alarm:EC , UC ,Shoc,AL,tEP 
,Ec-tE(Ec or Temperature) 
/independant from main trip 
*Al:Higher alarm level(Alhc) 
to OC,65~100%/Contact is 
closed after 3 sec from 
reaching setting alarm level 

 

 

Содержание DSP-VIP-PL

Страница 1: ...Voltage Current based Digital Multi function Motor Protection Relay DSP VIP PL PM...

Страница 2: ......

Страница 3: ...gnostics table 11 Input Output Terminal 12 Relay Output 13 Presetting Description 14 Control Key Operation 15 Time based Trip Relay Output 16 Trip Indication 17 Current Range Table for external CT 18...

Страница 4: ...Multi function Motor Protection Relay 1 System Construction DSP VIP PL Panel Mounting Type DSP VIP PM Panel Flush Mounting Type Cable RS232 Comm Module Converter Display Meter 1 2 32 RS232 OR RS232 R...

Страница 5: ...der CT Block 3 Colour LED Power G Operating R Trip Y Functional DIP SW 9 PIN D SUB RS 232 Loader Test Reset 9 PIN D SUB RS 232 Comm Module Air Vent Screw Hole DIN Rail Moving Tip IN OUT Termial Lock H...

Страница 6: ...w Hole 9PIN D Sub RS 232 Converter DIP SW 4P Termination Resistence 485 422 Outside View Inside View Status LED 9 PIN D Sub RS232 Converter by Cable Connector Menu Bar 5 Digit Display OFF Phase LED ON...

Страница 7: ...set value during motor run done by adjusting SET Mode key Press SET key during a motor run then search mode neccessary to check consequently name of mode preset value is shown alternatively not possib...

Страница 8: ...can not start hence need to preset OFF in TEP mode to make a motor start Various and multiple trip output of Main and Aux relay Main 1a 97 98 energized trip with an output of C SC F MC R together AUX...

Страница 9: ...if necessary To response for RS 485 422 Modbus RTU To select one of RS 485 and 422 Simply selectable in DIP SW inside communication module CM 44 To put easily terminattion resistence in extreme end un...

Страница 10: ...Acceptable with both rating of ZCT High Level Protetion Class...

Страница 11: ...ommunication Module DSP CM 44 MWR S a the interface between Note PC and DSP directly by RS232 Note If DSP is connected through a 9 pin port in PC the wiring must be changed as follows b Communication...

Страница 12: ...Note The detail about MWR S 485 recorder is described in the manual for MWR S Various and Multiple Indication...

Страница 13: ...rrent O O Under Load Under Current O O Over Voltage O O Under Voltage O O Phase Loss by Line Voltage O O Phase Loss by Load Current O O Phase Reverse by Line Voltage O O Phase Reverse by Load Current...

Страница 14: ...with Note PC O O 6 Technical Specification Division Description Line Voltage 3 phase AC 100V 600V 50 60Hz Voltage setting range AC 110V over 110V 150V under 70 110V AC 220V over 220V 290V under 150 22...

Страница 15: ...hase loss trip delay time PLc based on load current 1 5sec definite Allowable tollerance Voltage 3 Current C 2A 0 1A C 2A 5 Time t 2 sec 0 1sec t 2 sec 5 Power factor 5 KW KWH 5 Cos Phi 0 6 Control po...

Страница 16: ...Conducted Disturbence Test IEC 60255 22 6 10V Level 3 Digital Communication with communication module recorder Physical feature RS 485 RS 422 CM 44 8 RS485 MWR S Address 1 250 Speed MWR S 9 6 19 2 38...

Страница 17: ...if the preset current unbalance rate is kept over 8 sec rate max curr min curr max curr 100 Voltage Unbalance Trip is done if the preset voltage unbalance rate is kept over preset time rate max volta...

Страница 18: ...d by load current Trip time 1 5 sec definite OFF is possible in this mode If phase loss is happened auto reset is not possible but manual reset Reverse Phase by line voltage This protection is identif...

Страница 19: ...ange 1 65535 next to zero to clear existing accumulated KWH refer a case of KWH Load factor by bar graph calculating as followed actual load curr preset curr 100 or actual load kw preset load kw 100 L...

Страница 20: ...y Initial state display When the control power is on the disply is shown in the order as follows LOP default tE no if PT 100 is not connected version NO ON OFF control command position one of LOP MCC...

Страница 21: ...possible matched with external CT Division Description Feature Terminal Input 3P 1P 3P 1P 3 phase Single phase Load current KW C External ZCT Z1 Z2 200 1 5mA 200 100mV Control Power A1 A2 85 260VAC 50...

Страница 22: ...een Power ON stop state Yellow Trip Output MAIN TRIP 97 98 VOLTAGE TRIP 27 28 Changeable to ALLc AUX TRIP 07 08 4 20mA SC F MC R C1 COMMON SC F Starting contactor forward contactor MC R Main contactor...

Страница 23: ...n Au o mode one of OFF Ec uc Shoc Al tEP Ec tE SS tr Ec ta Ec tb OFF same as Main Trip SS tr trip caused by short circuit same as main trip Main Trip it means motor is stopped like a case of main trip...

Страница 24: ...p output comes out through this output 13 Preset Description 13 1 Main Mode Mode Function range Description Factory Setting value P0000 Password Press SET button to have a preset Input a factory setti...

Страница 25: ...value current and it is default condition that previous KW mode is not appeared even though C is selected the indication and the protection in conjunction with line voltage can be executed if line vol...

Страница 26: ...mode is displayed like SS In case of the usage with external CT is naturally based on 0 2A 6A AUX 07 08 output is available to operate MCCB with enough current capacity as SS tr is selected in Auo mod...

Страница 27: ...ine ON to make a trip to protect phase loss based on line voltage within 0 5 sec In case 3 phase is normal power off state this mode is not worked Auto reset is not possible but manual reset on rP oFF...

Страница 28: ...s elapsed b Frdt oFF setti ng value to preset transferred time for SC F MC R Adjustable time 1sec 5 min SC end MC start transit time 0 2sec dt is available for each contactor while the transaction is...

Страница 29: ...F setting value to preset lower alarm level rate to OC This mode is disable state like __ in case voltage value is preset in LInE mode The preset in this mode is possible only in case LInE mode is in...

Страница 30: ...ted KWH is 99999999 To clear press UP firstly keeping pressed UP nextly press DN key then keep 1 sec under pressed state of both key finally release DN key earlier than UP key 0 rESEt Hr AuL to decide...

Страница 31: ...return to main mode trip information in order faulty phase and faulty value is appeared alternatively more detailed information can be retrieved by note PC directly or remote center trip Addr Setting...

Страница 32: ...caribration for phase R voltage 0 vsPEr to have a caribration for phase S voltage 0 vtPEr to have a caribration for phase T voltage 0 EcPEr to have a caribration for ground fault current tEPEr to hav...

Страница 33: ...m running state va to fix to 1 100 as power factor useful for the operation under the inverter Pa To decide a qualification of VIP in case of the communication auto VIP always dispatches a data Slave...

Страница 34: ...haracter of mode If there is no input for 15 sec or pressing Mode key VIP is entered into operating condition 2 Set Key Function After entering into posible state for setting each key acts its job as...

Страница 35: ...er FWD Forward operation REV Reverse operation Motor Stop To stop a motor in any case To check preset value of each mode during operation possible to check value and mode as pressing SET key once duri...

Страница 36: ...Shock Stall Protection Normal energized condition 15 4 Ground fault Protection In case of applying Main Trip Au o mode OFF In case of applying AUX trip for ground fault protection Au o mode Ec V t 27...

Страница 37: ...15 5 2 Level Higher Level Lower Level Alarm to Over Current 15 6 SC F MC R Transit time 0 2 sec...

Страница 38: ...t current Phase loss trip caused by phase loss of phase L2 in incomming voltage trip caused by phase loss of phase L2 in load part Reverse phase trip caused by reverse phase of phase L2 in incomming v...

Страница 39: ...voltage and trip cause is shown together as below while normal circulation for each factor is turned on then move forward to next indication factor Trip Display Cause Over voltage OP trip caused by ov...

Страница 40: ...1 600 0 6A 15A 1 3 15 5 0 8A 20A 1 4 20 5 1 2A 30A 1 6 30 5 1 6A 40A 1 8 40 5 2A 50A 1 10 50 5 2 4A 60A 1 12 60 5 3A 75A 1 15 75 5 4A 100A 1 20 100 5 4 8A 120A 1 24 120 5 3 6A 150A 1 30 150 5 8A 200A...

Страница 41: ...18 Time Current Characteristics 18 1 Over Current Over Load protection Inverse Curve 18 2 Ground Fault Protection Inverse Curve...

Страница 42: ...w State Output relay operation by Logic input C1 SC F P type C F Rtype Frdt OFF C1 M 5 series 1 Low High Motor Start C1 SC F C1 F C1 M Close 2 O 1 O Motor Stop C1 SC F C F C1 M Open 2 High Low rcs Rem...

Страница 43: ...nput C1 SC F P type C F Rtype Frdt OFF 1 Low High Forward Start C1 SC F C1 F close 2 O 2 O Forward Stop C1 SC F C1 F open 3 Low High Reverse Start C1 MC R C1 R close 2 O 2 O Reverse Stop C1 MC R C1 R...

Страница 44: ...ce diagram In order to use Logic input 3 for FWD REV operation Frdt mode in sub menu group must be preset OFF In case motor is stopped by the command of ON OFF Rmote sensor or external fault input not...

Страница 45: ...19 3 Y D Start 19 4 Foward Reverse Start...

Страница 46: ...19 5 Reactor start 20 Rotated Indication 20 1 Basic factor V I KW GR...

Страница 47: ...Example for Applied Communication 21 1 PC Directly DSP by RS 232 Data Input Monitoring In case VIP is connected with PC through 9 pin connector in PC a connection is changed as follows but if USB port...

Страница 48: ...l Line Connection b Serial Line Parallel Connection DSP CMB protocol converter 485 422 232 USB or 9 pin D sub T R TR TR termination resistance DSP CMB protocol converter 485 422 232 USB or 9pin D sub...

Страница 49: ...tion noise humidity etc The example picture for RJ45 is as follows Also the actual connection through screw terminal between Master and Slave DSP VIP in field bus system is as follows In the connectio...

Страница 50: ...same manner a seperation for this module from the converter must be done carefully If a seperation is needed inevitably give a force slightly to expand a clearance between a converter and a module on...

Страница 51: ...21 3 Center PC PLC DSP by RS 485 422 through Gateway...

Страница 52: ...oad latest samdsp v version nmber file provided by SamWha DSP Co web page or CD in C of your PC and run into the execution for this file 2 Check if c samdsp folder is created naturally or not 3 If you...

Страница 53: ...How to monitor a data in your PC 1 Unless you make other picture to be expressed by main bmp file you meet a window with Samwha DSP company image below It means everything is OK...

Страница 54: ...u want to put click a number matched in a bottom then you can put a motor symbol in proper position by operating a mouse Like this manner same process should be done for remained motor 4 After this ac...

Страница 55: ...is come 8 Then you could operate this protection relay as controllng and or monitoring in every screen How to analize recorded data in your PC In case MWR MWR S is used with VIP PM PL this is describ...

Страница 56: ...23 Dimension Converter Communication Module Converter Loader Display Meter Loader...

Страница 57: ...t rating 3 B 24VAC DC Control Power Z 85VAC 260VAC 90VDC 370VDC 4 7 50 60Hz Frequency Control Power 5 ZCT ZCT Embeded Not possible to use with external CT XX Option Exclusive Customer Order Available...

Страница 58: ...260VAC 50 60Hz 90VDC 370VDC with external ZCT 0 2 6A with external CT DSP VIP PM70Z7 PC 0 2 70A Converter Display Meter Comm Module Optional Function program 85VAC 260VAC 50 60Hz 90VDC 370VDC with ext...

Страница 59: ...arks Cable DSP CABLE 12 1 2m DSP CABLE 18 1 8m DSP CABLE 30 3m DSP CABLE XX Over 3m ZCT DSP ZCT XX 00mA 1 5mA XX Inner diameter of ZCT DSP ZCT V XX 100mA 100mV Loader DSP ID PL Input Device Loader Dis...

Страница 60: ...vided through an insulated transformer and a proper fuse above mentioned otherwise RS 232 communication could be interfered 3 fastening screw a connection between a terminal of DSP and a wire must be...

Отзывы: