Self-diagnostics
*Main trip relay will be trip(energized) after count
down a preset o-time(dt or time of 550% in inverse)
in "Test" SW of converter or in press "CLR" SW
for 3 sec to check if a self-function is normal or
not.
Main contactor
Auto Close
*In case a line power is "on" again within a preset
time after a line power is "OFF" during a normal
operation,main contactor is closed automatically
after another preset time(DOMT)
*Shut Down Delay Time:1~5sec
/Adjustable
*Delay On Make Time:0(instant)~25sec/
Adjustable by 5sec unit
*Expression in mode:eg/2-3:in case power is
"on" within 2sec after power-off,motor starts
after 15sec((3 is matched with 15sec)
from the instant of power-on
10. Self-diagnostics table
Discription
Message display
Initial state display
When the control power is on,the disply is shown in
the order as follows: LOP(default)
tE-no(if PT-
100 is not connected)
version NO.--> ON/OFF
control command position(one of LOP, MCC/display
meter , rcs and PC)
485 communication error
LED on the communication module is not turned on
or not flickered
Fault for internal current board
cu-no
Fault for internal voltage board
vo-no
Fault for GR protection function in
internal main board
Ec-no
ZCT disconnection
Ec-ct
PT100 disconnection
te-no;not possible to rum if a value is preset in"tep"
mode
Latest measured temperature
greater than preset temperature
"tep" and "latest measured value" is appeared
alternatively/not possible to run if preset value is not
changed
Test:by Test SW in converter or
"CLR" SW
Main trip(97-98) is tripped after counting down
preset o-time in definite T-I(550% time in inverse T-
I)/the number of lighted LED is matched with
counted time
Содержание DSP-VIP-PL
Страница 1: ...Voltage Current based Digital Multi function Motor Protection Relay DSP VIP PL PM...
Страница 2: ......
Страница 10: ...Acceptable with both rating of ZCT High Level Protetion Class...
Страница 12: ...Note The detail about MWR S 485 recorder is described in the manual for MWR S Various and Multiple Indication...
Страница 37: ...15 5 2 Level Higher Level Lower Level Alarm to Over Current 15 6 SC F MC R Transit time 0 2 sec...
Страница 45: ...19 3 Y D Start 19 4 Foward Reverse Start...
Страница 46: ...19 5 Reactor start 20 Rotated Indication 20 1 Basic factor V I KW GR...
Страница 51: ...21 3 Center PC PLC DSP by RS 485 422 through Gateway...
Страница 56: ...23 Dimension Converter Communication Module Converter Loader Display Meter Loader...