Installing the Product
English 8/2019. Rev 0.0
41
3.10.2
SMU and SMPS Assembly Installation
Important
Attach each SMU to its rack frame with four M5 x 10L screws. (Torque: 5.1–6.1 Nm [50–60 kgf
cm])
Verify that the torque setting is correct.
1.
Insert the SMU through the front of the rack as shown in Figure 3-19: Inserting SMU
Figure 3-19: Inserting SMU
2.
After all SMU’s are inserted in the rack frames, attach each to the rack frame with four M5 x 10L bolts. (Torque: 5.1–6.1 Nm
[50–60 kgf cm])
Figure 3-20: Attaching a SMU to a Rack Frame
3.
After all SMU’s are inserted into the rack frame, connect the ground cable.