Installing the Product
English 8/2019. Rev 0.0
111
NOTICE
The Rack BMS configuration cable, System BMS configuration cable and Ethernet cable must be
made by the customer or installer according to the following PIN map.
Figure 3-130: Rack BMS Configuration Cable Pin Map
Table 3-11: Rack BMS Configuration Cable Pin Map
Connection A
Connection B
Connector
Pin No.
Signal
Connector
Pin No.
Signal
D-SUB (Female)
1
-
J21SF-06V-KX-L
1A
GND Ground
2
CAN Low
2A
-
3
CAN Ground
3A
-
4
-
1B
CAN Low
5
-
2B
CAN High
6
-
3B
-
7
CAN High
8
-
9
-