3
.
Installing the Product
Confidential
120
English 8/2019. Rev 0.0
Figure 3-145: BATTMON Splash Window
5.
Select the CAN [IXXAT] device from the list and click “Connect”. If no device is shown, disconnect the IXXAT USB-to-CAN
device from the computer and reinstall the device driver.
Figure 3-146: Rack BMS - CONFIG connection window
NOTICE
When the USB-to-CAN device is not connected to your computer, the CONNECT button will not
work.
6.
Select “RACK #001” from the drop-down menu. This is the factory default setting.
- Click on the checkbox to write the value.
- Double-click the values under “Write Value” column to change the write values.
- For CAN ID #1, write value is 0x2001. For CAN ID #2, the value is 0x2002.
- Write the number of module BMS per rack. In case of 136S battery, the number of module BMS is 17. (8 cells per module
BMS)
- Click “[WRITE] To BMS B’d” button to write the checked values to the Rack BMS.
- Click “APPLY [BMS RESET]” to reset the BMS with the written parameters.
Содержание 136S