Select initialization mode:
Initialization mode
Default: MAX
Turn
→
Code
6
Press
Turn
→
SUB
Press
to confirm the
SUB
initialization
mode.
Enter direction of action:
Direction of action
Default:
ää
Turn
→
Code
7
Press
, Code
7
blinks.
Turn
→
Direction of action (
ää
/
äæ
)
Press
Deactivate travel limit:
Travel limit
Default: 100.0
Turn
→
Code
11
Press
, Code
11
blinks.
Turn
→
No
Press
Change pressure limit and control parame-
ters:
Note:
Do not change the pressure limit
(Code
16
). Only change the control param-
eters K
P
(Code
17
) and T
V
(Code
18
) if the
settings of the replaced positioner are
known.
Pressure limit
Default: No
KP stage
Default: 7
TV stage
Default: 2
Turn
→
Code
16/17/18
Press
, Code
16/17/18
blinks.
Turn
and set the selected control param-
eter.
Press
to confirm setting.
Enter closing direction and blocking posi-
tion:
Closing direction
Direction of rotation causing
the valve to move to the
CLOSED position (view onto
positioner display)
Default: CCL (counterclock-
wise)
EB 8387-3S EN
57
Start-up – Settings
Содержание TROVIS SAFE 3731-3
Страница 5: ...EB 8387 3S EN 5...
Страница 92: ...92 EB 8387 3S EN...
Страница 93: ...EB 8387 3S EN 93...
Страница 94: ...94 EB 8387 3S EN...
Страница 95: ...EB 8387 3S EN 95...
Страница 96: ...96 EB 8387 3S EN...
Страница 97: ...EB 8387 3S EN 97...
Страница 98: ...98 EB 8387 3S EN...
Страница 101: ...EB 8387 3S EN 101...
Страница 102: ...102 EB 8387 3S EN...
Страница 103: ...EB 8387 3S EN 103...