7.5.1 Initialization based on MAX
maximum range
The positioner determines travel/angle of
rotation of the closing member from the
CLOSED position to the opposite side and
adopts this travel/angle of rotation as the
operating range from 0 to 100 %.
Enable configuration:
Note:
If no settings are entered within
120 seconds, the enabled configuration
function becomes invalid.
Configuration enabled
Default: No
Turn
→
Code
3
, display:
No
Press
, Code
3
blinks.
Turn
→
YES
Press
, display:
Select initialization mode:
Initialization mode
Default: MAX
Turn
→
Code
6
Press
Turn
→
MAX
Press
to confirm the
MAX
initialization
mode.
Start initialization:
Initialization
Fail-safe position setting
Progress indicated until
initialization starts
Turn
→
Code
0
Press
, Code
0
blinks.
Turn
→
Init
Press
. The setting of the fail-safe position
AtO
or
AtC
appears.
Keep
pressed down for 6 seconds.
Initialization starts after the progress indica-
tion has stopped.
The nominal travel/angle of rotation is indi-
cated in % after initialization. Code
5
(nomi-
nal range) remains locked. The parameters
for travel/angle range start (Code
8
) and
travel/angle range end (Code
9
) can also
only be displayed and modified in %.
For a reading in mm/°, enter the pin posi-
tion (Code
4
).
52
EB 8387-3S EN
Start-up – Settings
Содержание TROVIS SAFE 3731-3
Страница 5: ...EB 8387 3S EN 5...
Страница 92: ...92 EB 8387 3S EN...
Страница 93: ...EB 8387 3S EN 93...
Страница 94: ...94 EB 8387 3S EN...
Страница 95: ...EB 8387 3S EN 95...
Страница 96: ...96 EB 8387 3S EN...
Страница 97: ...EB 8387 3S EN 97...
Страница 98: ...98 EB 8387 3S EN...
Страница 101: ...EB 8387 3S EN 101...
Страница 102: ...102 EB 8387 3S EN...
Страница 103: ...EB 8387 3S EN 103...