Press
The positioner changes to automatic mode
(AUTO). The current valve position is indi-
cated in % on the display.
Note:
If the positioner shows a tendency to
hunt in automatic operating mode, the pa-
rameters K
P
and T
V
must be slightly cor-
rected. Proceed as follows:
–
Set T
V
(Code
18)
to 4.
–
Reduce K
P
(Code
17
) until the positioner
shows a stable behavior.
Zero point correction
Finally, if process operations allow it, the
zero point must be calibrated as described
in section 7.6.
7.6
Zero calibration
In case of discrepancies with the closing po-
sition of the valve, e.g. with soft-sealed
plugs, it may become necessary to
recalibrate the zero point.
NOTICE
The valve briefly moves from the current
travel/angle of rotation position to the
closed position.
Note:
The positioner must be connected to
the supply air to perform the zero calibra-
tion.
Enable configuration:
Turn
→
Code
3
, display:
No
Press
, Code
3
blinks.
Turn
→
YES
Press
, display:
Perform zero calibration:
Initialization mode
Default: MAX
Turn
→
Code
6
Press
, Code
6
blinks.
Turn
→
ZP
Press
Turn
→
Code
0
EB 8387-3S EN
59
Start-up – Settings
Содержание TROVIS SAFE 3731-3
Страница 5: ...EB 8387 3S EN 5...
Страница 92: ...92 EB 8387 3S EN...
Страница 93: ...EB 8387 3S EN 93...
Страница 94: ...94 EB 8387 3S EN...
Страница 95: ...EB 8387 3S EN 95...
Страница 96: ...96 EB 8387 3S EN...
Страница 97: ...EB 8387 3S EN 97...
Страница 98: ...98 EB 8387 3S EN...
Страница 101: ...EB 8387 3S EN 101...
Страница 102: ...102 EB 8387 3S EN...
Страница 103: ...EB 8387 3S EN 103...