F
Function
FS
Sys.
Comment
10 Intermediate heating af-
ter 20 min for 10 min
see page 48
On
2, 3
On = active, only if CO2 F06-0
Off = Priority of drinking water heating system
11 FS2 Control sensor
see page 51
On
5
On = FS2 Control sensor for system with instantane-
ous water heater (Pt 1000)
Off = Processing thermostat, parameter: control val-
ve transit time (
15 s
)
12 Recognition of drinking
water tapping
see page 51
Off
5
Off = Recognition DW tapping with FS2
On = Recognition DW tapping, only if CO2 F11-1,
Option:
1
: Hydraulic pressure switch (HPS)
2: Return flow sensor drinking water (RfSDW)
Appendix A.4 Function block parameter CO2
Parameter
Symbol
F
FS
Unit
Value range
Day of thermal disinfection
05
3
0...7 (daily, Mon...Sun)
Storage set point thermal disinfection
05
70.0
°C
60.0 90.0
Start time thermal disinfection
START
05
0:00
0:00 23:30
Stop time thermal disinfection
STOP
05
4:00
0:00 23:30
Waiting time until HCP Off
STOP
06
600
s
120 600
Idle time
09
300
s
60 600
Control valve transit time
11
15
s
10 240
EB 5431 EN
67
Function block lists
Содержание TROVIS 5431
Страница 95: ...V Vacation for drinking water heating 51 66 Vacation periods 40 W Wall mounting 56 EB 5431 EN 95 Index...
Страница 96: ......
Страница 97: ...Code number EB 5431 EN 97 Code number 1732...
Страница 98: ......
Страница 101: ......