System code number 4
Weather-compensated heating control system with drinking water heating in a storage
tank charging system
4
Optional priority function for the drinking
water heating circuit designed as reverse
control or set-back control, see chapter
5.5.6
4
If the system is not equipped with storage
tank sensor(s), the storage tank tempera-
ture is regulated by the mechanical tem-
perature regulator (self-operated regula-
tor). The storage charging pump operates
on a time schedule.
4
If the system is equipped with storage
tank sensor(s), the drinking water heating
system operates according to the requests
issued by the storage tank sensors. If the
temperature in the storage tank falls be-
low the limit value for start-up, the stor-
age charging pump is activated. If the
temperature in the storage tank exceeds
the value for deactivation of the system,
the storage charging pump is deactivated
and finishes the charging process. The
self-operated temperature regulator then
regulates the charging temperature.
34
EB 5431 EN
System descriptions
F
RF
FS1
FS2
HCP
SCP
Self-operated
regulator
STS1
STS2
RS
OS
DW
Circ.
CP
CW
RfS
Fig. 7
⋅
System code number 4