9
Technical data
Inputs
Depending on which system code number has been selected
Sensor inputs
Max. 7 configurable inputs for temperature sensors (PTC or Pt1000)
2-phase circuit
2 flow temperature sensors
1 room temperature sensor
1 outdoor temperature sensor
1 return flow temperature sensor
2 storage tank temperature sensors
Binary inputs
Storage tank thermostat
Additional inputs
Input for potentiometer or room sensor with set point correction and
mode switch
Analog input
0 to 10 V, (Ri= 20 k
Ω
)
Outputs
Depending on how the controller has been configured
Control signal
Three-step signal: load rating: 20 to 250 V AC; 0.5 A AC
On-off signal: load rating: 20 to 250 V AC; 0.5 A AC
Binary outputs
optional
4 outputs for controlling the pump
non-floating: 230 V AC, 2 A AC (cos
ϕ
>0.5)
3 outputs (BO1 to BO3) for pump management and collective error
message: 30 V, 100 mA AC/DC
or BO3 only: 230 V 50 mA AC/DC
Analog output
0 to 10 V, load > 2 k
Ω
Auxiliary power
230 V AC (+10%, -15%), 48 to 62 Hz, power consumpt. appr. 3 VA
Ambient temperature
0 to 50 °C (operation)
−
10 to 60 °C (transportation and storage)
Degree of protection
IP 40 according to IEC 529
Class of protection
I according to VDE 0106
Degree of contamination
2 according to VDE 0110
Overvoltage category
II according to VDE 0110
Humidity rating
F according to VDE 40040
Noise immunity
According to EN 50082 Part 1
Noise emission
According to EN 50081 Part 1
Weight
Approx. 0.6 kg
EB 5431 EN
63
Technical data
Содержание TROVIS 5431
Страница 95: ...V Vacation for drinking water heating 51 66 Vacation periods 40 W Wall mounting 56 EB 5431 EN 95 Index...