Appendix E Resistance values of temperature sensors
Resistance thermometer with PTC component
Outdoor temperature sensor: Type 5224, to measure flow and return flow temperature: Type 5264 and
5265,
to measure storage tank temperature: Type 5264
°C
−
20
−
10 0
+10 +20 +25 +30 +40 +50 +60 +70 +80 +90 +100 +110 +120
Ω
694 757 825 896 971 1010 1050 1132 1219 1309 1402 1500 1601 1706 1815 1925
Sensor for room temperature with remote control Type 5244
°C
+10 +15 +20 +25 +30
Ω
679 699 720 741 762
Resistance thermometer with Pt 1000 component
Outdoor temperature sensor: Type 5227, to measure flow and return flow temperature: Types
5207-21, 5207-26, 5207-27, 5277 (thermowell required) and 5267 (contact sensor with cable of 3 m
length), to measure storage tank temperature: Types 5207-46, 5207-47 and 5207-48, room tempera -
ture sensor: Type 5257 and room temperature sensor with remote control: Type 5257-4.
°C
−
35
−
30
−
25
−
20
−
15
−
10
−
5
0
5
1
Ω
862.5
882.2
901.9
921.6
941.2
960.9
980.4
1000.0
1019.5
1039.0
°C
15
20
25
30
35
40
45
50
55
60
Ω
1058.5
1077.9
1097.3
1116.7
1136.1
1155.4
1174.7
1194.0
1213.2
1232.4
°C
65
70
75
80
85
90
95
100
105
110
Ω
1251.6
1270.7
1289.8
1308.9
1328.0
1347.0
1366.0
1385.0
1403.9
1422.9
°C
115
120
125
130
135
140
145
150
Ω
1441.7
1460.6
1479.4
1498.2
1517.0
1535.8
1554.5
1573.1
86
EB 5431 EN
Resistance values of temperature sensors
Содержание TROVIS 5431