Parameter settings
Heating circuit parameters (PA1, CO1)
Parameter
Current setting
Unit
Range of values
Gradient of characteristic
Heating characteristic gradient
0.2 3.2
Set-back of flow temperature
for reduced operation
°C
0.0 50.0
Level of heating characteristic
°C
−
30.0 +30.0
Level of return flow character.
0.2 3.2
Level of return flow character.
°C
−
30.0 30.0
4-point characteristic
Point 1
Point 2
Point 3
Point 4
Outdoor temperature
°C
−
30.0...+50.0
Flow temperature
°C
20.0 130.0
Return flow temperature
°C
20.0 90.0
Set-back difference
°C
0.0 50.0
Maximum flow temperature
°C
20.0 130.0
Minimum flow temperature
°C
20.0 130.0
Maximum return flow temperature
°C
20.0 90.0
Minimum return flow temperature
°C
20.0 90.0
Limit values of the
outdoor temperature
~ to return to rated operation
when in reduced operation
°C
−
30.0 ~for
deactivation
when in redu-
ced operation
~ for deactivation when in
reduced operation
°C
~ to return to
rated operation
when in redu-
ced operation
50.0
~ for summer operation
°C
0.0 50.0
Room temperature set points
Room set point
°C
10.0 40.0
88
EB 5431 EN
Configured data