Code
no.
Parameter
– Readings,
values [default setting]
Description
Note:
Codes with marked with an asterisk (*) must be enabled with
Code 3
prior to configuration.
E4 – Unassigned –
E5* Activate PST tolerance band
monitoring
[No] · YES
Activates PST tolerance band monitoring (YES) or deactivates it
(No)
E6* PST tolerance band
0.1 to 100.0 % · ESC, [5.0]
The test is canceled when the deviation in valve position (in rela-
tion to the upper range value of the step) exceeds the adjusted
value.
E7* Max. test duration
30 to 25000 s · ESC [30]
The test is canceled when the maximum test duration is reached.
E8 – Unassigned –
E9* Reset 'Partial stroke test pa-
rameters'
Resets partial stroke test parameters
F0
No test available
F1
– Unassigned –
F2
x cancelation
The test was canceled.
The valve position fell below the
x monitoring value
(
Code 49 -
E1
).
F3
D
p_out cancelation
The test was canceled.
The change in signal pressure (
D
p_out) fell below or exceeded
the reference value (
Code 49 - A9
).
F4
Tolerance band exceeded
The deviation of the valve position exceeded the adjusted
PST tol-
erance band
(
Code 49 - E6
).
F5
Max. test duration ex-
ceeded
The test was canceled.
The
Max. test duration
(
Code 49 - E7
) was reached.
F6
Test canceled manually
F7
Measured data memory full
The
Sampling time
(
Code 49 - d9
) is too low. After recording
100 data points per variable, logging is stopped, but the test
continues until it is completed.
F8
Cancelled by internal sole-
noid valve/forced venting
The test was canceled.
The internal solenoid valve has been energized/the forced
venting has been activated.
EB 8384-6 EN
99
Code list
Содержание 3730-6
Страница 19: ...EB 8384 6 EN 19...
Страница 51: ...EB 8384 6 EN 51...
Страница 113: ...EB 8384 6 EN 113...
Страница 114: ...114 EB 8384 6 EN...
Страница 115: ...EB 8384 6 EN 115...
Страница 116: ...116 EB 8384 6 EN...
Страница 117: ...EB 8384 6 EN 117...
Страница 118: ...118 EB 8384 6 EN...
Страница 119: ...EB 8384 6 EN 119...
Страница 120: ...120 EB 8384 6 EN...
Страница 123: ...EB 8384 6 EN 123 diagnostic functions 11 Z Zero calibration 68 Index...