Code
no.
Parameter
– Readings,
values [default setting]
Description
Note:
Codes with marked with an asterisk (*) must be enabled with
Code 3
prior to configuration.
4*
Pin position
[No] · 17, 25, 35, 50, 70,
100, 200 mm · 90° with ro-
tary actuators · 300 mm with
piston actuators · ESC
NOTICE
If you select a pin
position in
Code 4
that is too
small, the positioner switches
to SAFE mode for reasons of
safety
The follower pin must be inserted into the correct pin position ac-
cording to the valve travel/angle of rotation.
For initialization using NOM (nominal range) or SUB (substitute
calibration), the pin position must be entered.
For initialization using MAX, MAN and MAN2, the pin position
is not required, however, it is required under Code 5 to display
the nominal range.
Pin position
Default
Adjustment range
Code 4
Code 5
Code 5
17
7.5
3.6 to 17.7
25
7.5
5.0 to 25.0
35
15.0
7.0 to 35.4
50
30.0
10.0 to 50.0
70
40.0
14.0 to 70.7
100
60.0
20.0 to 100.0
200
120.0
40.0 to 200.0
90°
90.0
24.0 to 100.0
300
200.0
60.0 to 300.0
5*
Nominal range
[15.0] mm or angle °
ESC
For initialization using NOM (nominal range) or SUB (substitute
calibration), the nominal range must be entered. The possible ad-
justment range depends on the pin position from the table for
Code 4.
After initialization to the maximum range (MAX), the maximum
nominal travel/angle reached on initialization is displayed.
6*
Initialization mode
(init
mode)
[MAX] · NOM · MAN
MAN2 · SUB
KP · ZP
ESC
MAX: Maximum range · For simple start-up of valves with two
clearly defined mechanical end positions · The positioner
determines travel/angle of rotation of the closing
member from the CLOSED position to the opposite stop
in the actuator
NOM: Nominal range · For all globe valves · The positioner de-
termines travel/angle of rotation of the closing member
from the CLOSED position to the specified nominal
range
MAN: Manual setting 1 · For all globe valves with unknown
nominal range (OPEN position) · The positioner deter-
mines travel/angle of rotation from the manually se-
lected OPEN position (100 %) to the CLOSED position
84
EB 8384-6 EN
Code list
Содержание 3730-6
Страница 19: ...EB 8384 6 EN 19...
Страница 51: ...EB 8384 6 EN 51...
Страница 113: ...EB 8384 6 EN 113...
Страница 114: ...114 EB 8384 6 EN...
Страница 115: ...EB 8384 6 EN 115...
Страница 116: ...116 EB 8384 6 EN...
Страница 117: ...EB 8384 6 EN 117...
Страница 118: ...118 EB 8384 6 EN...
Страница 119: ...EB 8384 6 EN 119...
Страница 120: ...120 EB 8384 6 EN...
Страница 123: ...EB 8384 6 EN 123 diagnostic functions 11 Z Zero calibration 68 Index...