7.9
Reset to default values
A reset allows the positioner to be reset to
the default settings. To reset the positioner,
the options Diag, Std and DS are available
in
Code 36
. Table 8 lists the reset functions.
Note: Code 36 – DS
is usually selected
when the valve is mounted in another posi-
tion or when the positioner is to be mounted
to another valve.
Performing a reset does not necessarily
mean the positioner must be re-initialized.
Enable configuration:
Turn
®
Code 3
, display:
No
Press
, Code 3 blinks
Turn
®
YES
Press
, display
Reset start-up parameters:
Reset
Default
No
Turn
®
Code 36
, display:
– – –
Press
, Code 36 blinks
Turn
®
DIAG/STD/DS
Press
. The parameters are reset depend-
ing on the option selected. Refer to Table 9.
EB 8384-6 EN
71
Start-up – Settings