![Samson 3730-6 Скачать руководство пользователя страница 98](http://html2.mh-extra.com/html/samson/3730-6/3730-6_mounting-and-operating-instructions_3887082098.webp)
Code
no.
Parameter
– Readings,
values [default setting]
Description
Note:
Codes with marked with an asterisk (*) must be enabled with
Code 3
prior to configuration.
d3* Upper range value
0.0 to 100.0 % · ESC, [90.0]
Final value of the test
d4* Activate ramp function
No · [YES]
YES:
The valve is ramped through the test range within the
adjusted ramp time.
No:
The valve is moved in steps through the test range (step
response).
d5* Ramp time (decreasing)
0 to 9999 s · ESC, [45]
Time period in which the valve moves through the operating
range from the closed to the open position
The time to move from
Lower range value
(
Code 49 - d2
) to
Upper range value
(
Code 49 - d3
) is calculated:
Upper range value – Lower range value
/ 100 x
Ramp time (in-
creasing)
d6* Ramp time (increasing)
0 to 9999 s · ESC, [45]
Time period in which the valve moves through the operating
range from the open to the closed position
The time to move from
Upper range value
(
Code 49 - d3
) to
Lower range value
(
Code 49 - d2
) is calculated:
Lower range value – Upper range value
/ 100 x
Ramp time (de-
creasing)
d7* Settling time before starting
test
1 to 240 s · ESC, [10]
Settling time between reaching the upper range value (
Code 49 -
d3
) and the valve moving through the test range in the reverse
direction
d8* Waiting time after step
change
1.0 to 240.0 s · ESC, [2.0]
Waiting time between step change from
Lower range value
(
Code 49 - d2
) to
Upper range value
(
Code 49 - d3
) and vice
versa
d9* Sampling time
[0.2] to 250.0 s · ESC
Time interval between measuring data
E0* Activate x monitoring
No · [YES]
Activates x monitoring (YES) or deactivates it (No)
E1* x monitoring value
–10.0 to 110.0 % of the en-
tire travel · ESC, [85.0]
The test is canceled when the valve moves below the adjusted
value.
E2 – Unassigned –
E3 – Unassigned –
98
EB 8384-6 EN
Code list
Содержание 3730-6
Страница 19: ...EB 8384 6 EN 19...
Страница 51: ...EB 8384 6 EN 51...
Страница 113: ...EB 8384 6 EN 113...
Страница 114: ...114 EB 8384 6 EN...
Страница 115: ...EB 8384 6 EN 115...
Страница 116: ...116 EB 8384 6 EN...
Страница 117: ...EB 8384 6 EN 117...
Страница 118: ...118 EB 8384 6 EN...
Страница 119: ...EB 8384 6 EN 119...
Страница 120: ...120 EB 8384 6 EN...
Страница 123: ...EB 8384 6 EN 123 diagnostic functions 11 Z Zero calibration 68 Index...