10 | SAMLEX AMERICA INC.
SECTION 3 |
Installation
3.4.1 Step1: Battery Connection
WARNING!
RISK OF EXPLOSION OR FIRE! NEVER SHORT CIRCUIT BATTERY POSITIVE (+)
AND NEGATIVE (-).
MISE EN GARDE!
RISQUE D'EXPLOSION OU D'INCENDIE! NE COURT-CIRCUITEZ JAMAIS LA
BATTERIE POSITIF (+) ET NÉGATIF (-).
Refer to Fig 3.2
Before the battery is connected, make sure that battery voltage is greater than 8V so as to start
up the controller. If the battery system voltage is 24V, make sure the battery voltage is not less
than 18V to ensure that battery system voltage is correctly sensed as 24V (
auto sensing feature for
battery system voltage will erroneously sense voltage < 18V as 12V battery system
). Battery system
voltage will be sensed automatically when the controller starts up for the first time. 15A fuse "F1"
is used to protect the cable run from the battery to the charge controller against short circuit. Install
the fuse not more than 7" from the battery Positive terminal. Do not insert the fuse at this time.
3.4.2 Step 2: Load Connection through Load Terminals (Limited to 10A)
Refer to Fig 3.2
The Load Terminals of the controller can be connected to such electrical devices as lights and other
devices with load current of up to 10A. Controller provides power to the load(s) through the battery.
When load(s) are fed from the Load Terminals, the controller will provide the following protec-
tions on the load side:
Protect the battery as follows:
-
Battery Low Voltage Alarm (≤12V/24V)
: Battery Status LED (
2, Fig 2.1
) will be steady ORANGE.
Output will still be available at Load Terminals. This condition will be auto reset at 12.2 / 24.4V
WARNING!
CURRENT OUTPUT ON THE LOAD TERMINALS IS LIMITED TO A MAXIMUM OF 10A.
IF HEAVIER LOADS DRAWING MORE THAN 10A LIKE INVERTER ETC. ARE REQUIRED
TO BE POWERED, CONNECT THEM DIRECTLY TO THE BATTERY THROUGH APPROPRI-
ATE FUSE "F2" THAT SHOULD MATCH THE DC INPUT CURRENT OF THE INVERTER.
THIS FUSE SHOULD ALSO BE INSTALLED WITHIN 7" OF THE BATTERY (+) TERMINAL.
MISE EN GARDE!
LA SORTIE DE COURANT SUR LES BORNES DE CHARGE EST LIMITÉE À UN
MAXIMUM DE 10A. SI DES CHARGES PLUS LOURDES TIRENT PLUS DE 10A
COMME UN ONDULEUR, ETC. DOIVENT ÊTRE ALIMENTÉS, CONNECTEZ-LES
DIRECTEMENT À LA BATTERIE VIA LE FUSIBLE APPROPRIÉ «F2» QUI DOIT
CORRESPONDRE AU COURANT D'ENTRÉE CC DE L'ONDULEUR. CE FUSIBLE DOIT
ÉGALEMENT ÊTRE INSTALLÉ À MOINS DE 7 "DE LA BORNE (+) DE LA BATTERIE.