a) Not less than the rated Continuous DC Input Current (Column 2)
b) Closest Standard Ampere rating of fuse has been used
c) Type of fuse: fast-acting, Current Limiting, UL Class
–
Type "Class T" as per
UL Standard 248-15 or Type "HrC" as per bS 88-2 / IEC60269-2
3.5.7 using Proper DC Cable termination
The battery end and the inverter end of the wires should have proper terminal lugs that will
ensure a firm and tight connection. Choose lugs to fit the wire size and the stud sizes on the
inverter and battery ends.
3.5.8 reducing rF interference
To reduce the effect of radiated interference, shield the wires with sheathing / copper foil /
braiding. for details, refer to Limiting Electro-Magnetic Interference" at Section 1.3.4.
3.5.9 taping battery wires together to reduce inductance
Do not keep the battery wires far apart. Keep them taped together to reduce their inductance.
reduced inductance of the battery wires helps to reduce induced voltages. This reduces ripple in the
battery wires and improves performance and efficiency. for details, refer to Limiting Electro-Magnetic
Interference" at Section 1.3.4.