53
21.
FUSE REPLACEMENT
Cut off power supply to the controller
before fuse replacement.
A 1.25A time-delay subminiature fuse with
minimum interrupting current of 100A should be
used, as per IEC 60127 standard. An example of
a fuse meeting the requirements is
Schurter
MXT-250 time-delay fuse
. To replace, open
controller's enclosure and replace burnt fuse with
a new one (Fig. 21.1).
Fig. 21.1 Fuse replacement
Record of changes
3.X.1 z dn 9-06-2014 First edition
The manufacturer reserves the right to
make changes in design and software
without prior notice.