
20
between
T1
and
T2
is between the values
dTonDHW
÷
dToffDHW
the controller will
calculate and set pump speed proportionally.
When
dToffDHW
is reached, the pump will
work at minimal speed (
Pmin
), below it will be
stopped.
After reaching preset temperature in priority
circuit, the controller will switch the circuit.
The pool circuit will work analogically, except
that the temperatures are calculated from
T1
and
T3
and the system uses auxiliary deltas
dTonPOOL
÷
dToffPOOL.
Pool exchanger
P2
pump is always switched on/off with delay as
specified in
tDLY
setting in relation to
P1
pump.
When the second circuit is heated up to
preset temperature, the collector pump is
stopped. It will be restarted, when on any circuit
the temperature drops by hysteresis value
(
HP1
), in accordance with priority setting.
If the collector temperature reaches
TCOLcr
value, the collector pump will be started
and the circuit will be switched to priority one in
order to reduce the collector temperature. It will
be stopped, when
T1
temperature drops below
T1<TCOLcr-HP1.
If Priority is set for
DHW
, the collector
unloading will be continued only to the time when
TDHWmax
is reached, and then the system
switches to the pool. In the pool circuit there is
no upper limit for discharging collector’s critical
temperature.
Switching
between
DHW/POOL
is
controlled through
H
output. The circuit operation
starts only when the switching time elapsed
(
tVALVE
).
Due to pool system, the scheme has no
night cooling function.
List of settings in
Adjustment
menu
TsDHW-
Reservoir temperature preset
TsPOOL-
Pool temperature preset
Priority-
Priority setting: reservoir (
DHW
) or
pool (
POOL
) loading.
Alarm TCOLcr –
Switching on (YES) or off (NO)
the
alarm
on
exceeding
TCOLcr
temperature. This function will not affect the
controller operation. If the parameter is set
as NO the controller will not alarm when
TCOLcr
temperature is exceeded at the
collector sensor.
13.8.
Solar thermal scheme G
Loading of DHW reservoir with solar collector and
boiler.
Fig. 13.7 Solar thermal scheme G
The collector pump will be started with
100% capacity, if the difference between
T1
and
T2
exceeds value of
dTonDHW
setting
and it will be working for the time specified in
parameter
tP
. If after this time the difference
between
T1
and
T2
is still above
dTonDHW
, the
pump speed will remain at 100%. If the said
difference between
T1
and
T2
drops below
dTonDHW,
the controller will start reducing the
pump speed, until the difference between
T1
and
T2
reaches the value specified as
dToffDHW
. If the difference between
T1
and
T2
is between the values
dTonDHW
÷
dToffDHW
,
the controller will calculate and set the pump
speed proportionally.
When
dToffDHW
is reached, the pump
will work at minimal speed (
Pmin
), below it will
be stopped.
If
TsDHW
temperature is reached for
sensor:
T2
- reservoir loading from collector will be
stopped;
T3
– reservoir loading from boiler will be
stropped.
The reservoir loading will be restarted,
when one of the temperatures
T2
or
T3
drops
below hysteresis
HP1
for
T2
or
HP2
for
T3
.
If the collector temperature
T1
reaches
the value of
TCOLcr
, then the collector pump will
be started (despite of reaching
TsDHW
temperature). It is aimed to reduce the
collector’s temperature. It will be stopped, when
T1
drops below
T1<TCOLcr-HP1, or
if the
reservoir temperature at
T2
sensor reaches the
value of
TDHWmax
.
List of settings in
Adjustment
menu
TsDHW-
Reservoir temperature preset
dTCO –
Minimal temperature difference between
T4
and
T3
that starts loading of DHW
reservoir from boiler circuit
CH
(starting
P2
pump).
Night cooling- Yes
enables/
NO
disables night
cooling mode in hours 0
00
÷5
00
.
Night cooling ON –
DHW reservoir temperature
(
T2
sensor), when exceeded at 0
00
if night
Содержание PCSol 300
Страница 2: ......
Страница 6: ......
Страница 7: ...OPERATING MANUAL PCSol 300...
Страница 28: ......
Страница 29: ...INSTALLATION MANUAL PCSol 300...
Страница 54: ......
Страница 55: ......
Страница 56: ...SALUS Controls ul Bielska 4a 43 200 Pszczyna Poland...