13.12.

 

Solar thermal scheme K 

Loading 

container-in-container type buffer with 

low-temperature CH system assist. 

 

Fig. 13.11 Solar thermal scheme K 

 

Collector  pump  will  be  activated  with 

100%  power,  when 

T1-T2 

difference  exceeds 

dTwlDHW 

value  and  will  operate  for 

tP 

parameter  time.  If  after  this  time 

T1  and  T2 

is 

still  higher  than 

dTwlDHW

,  then  the  pump  will 

still  operate  at  the  highest  output.  If  the 
aforementioned difference falls below 

dTwlDHW 

value,  the  regulator  will  start  to  gradually 
decrease  pump  output,  until  the  difference 
reaches 

dTwyDHW

  value.  When 

T1  and  T2 

difference  is  between 

dTwlDHW

  ÷ 

dTwyDHW 

values, the regulator will measure and adjust the 
output in a proportional manner. 
When 

dTwyDHW 

value  is  reached,  the  pump 

operates  at  its  minimum  output  (

Pmin 

parameter). 

Any  value  below  will  cause  it  to 

stop. 

  If  temperature  difference 

dTAB  (T3  and 

T4 

difference)

 

between 

buffer (T3 sensor) and 

CO  system  return 

(T4  sensor)  is  not  reached, 

P2

  output  (a  valve  controlling  return  from 

system)  will  redirect  return  water  to  buffer’s 
center.  If 

T3 

temperature  increases  above 

T4+dTAB, 

three-way  system  valve  will  be 

switched  in  buffer’s  bottom  direction,  and 

boiler  will  be  powered  by  water  from  boiler’s 
center.

 

“Presets” 

menu parameters list 

TzDHW –

 Preset container’s temperature 

A and 

B

dTAB- 

temperature  difference  between 

buffer 

and 

system return 

(on 

T3 

and 

T4 

sensors), 

after which the regulator switches three-way 
valve. 

P2 

is  enabled,  when 

dTAB 

difference 

(between 

T3  and  T4 

temperatures)  falls  by 

auxiliary hysteresis 

AH2. 

Night  cooling  –  YES 

enables  / 

NO 

disables 

night cooling mode between 0

00

÷5

00

 hours.

 

Cooling 

temp 

ON. 

– 

DHW 

container 

temperature  (on 

T2 

sensor),  if  exceeded, 

and  night  cooling  is  enabled,  the  regulator 
will begin the cool down at 0 AM.  

 

Cooling  temp.  OFF 

– 

DHW 

container 

temperature  (on 

T2  sensor) 

to  which  the 

regulator  will  be  cooling  down  the  container 
(if  night  cooling  function  is  enabled  and 

Cooling temp. ON 

temperature is exceeded 

between 0

00

÷5

00

). 

TCOLkr  alarm  – 

Enabling  (YES)  or  disabling 

(NO)  of  the  alarm  of  exceeding 

TCOLkr 

temperature. This function does not influence 
regulator’s operation. If the parameter is set 
to NO, the regulator will not set off an alarm 
after 

exceeding 

TCOLkr 

collector’s 

temperature. 

13.13.

 

Solar thermal scheme L 

DHW  tank  is  loaded  by  two  solar  collector 

sets  oriented  towards  two  points  of  compass 
using  one  pump  group  and  collector  circuit 
separating valve. 

 

Fig. 13.12 Solar thermal scheme L 

 

Regulator  selects  the  solar  collector  of 

higher  temperature  to  operate.  Solar  collector 
serving  pump  is  activated  with  100%  capacity 
once  the  difference  of 

T1  or  T3 

(subject  to  the 

solar collector selected) and 

T2

 has exceeded the 

value of 

dTonDHW. 

The pump will work over the 

time  set  in 

tP

P2

  valve  is  set  at  the  position 

appropriate  to  switch  the  system  into  selected 
solar collector. If, upon elapsing of this time, the 
difference of 

T1 or T3

 and 

T2

 is still in excess of 

dTonDHW

  value,  the  pump  rpm  value  will 

remain  set  at  100%  all  the  time.  Once  the 
difference between 

T1 or T3

 and 

T2

 has dropped 

below 

dTonDHW 

value, regulator starts reducing 

pump  rotary  speed  until  the  difference  of 

T1  or 

T3

  and 

T2

  has  reached  the  value  set  in 

dToffDHW

.  In  case  the  difference  of 

T1  or  T3

 

and 

T2

 falls within the range from 

dTonDHW

 to 

dToffDHW

, the regulator computes and sets the 

rpm value proportionally. 

Once  the  difference  of 

T1  or  T3

  and 

T2

 

has  reached  the  value  set  in 

dToffDHW

,  the 

pump  runs  with  minimum  rpm  value  (

Pmin 

parameter) and in case it has dropped below this 
value, the pump stops.   

If,  in  case  of  operation  with  one  solar 

collector, temperature of the second collector has 
grown above the temperature of the first one (or 
v.v.)  and  the  value  of 

dTonDHW

  has  been 

reached,  the  regulator  switches  over  the  solar 
collector circuit.  

Содержание PCSol 300

Страница 1: ...CLOCK CLOCK SUSTAIN TEMPORARY POWER HEAD OUTPUT ANTI FREEZING GRAPHIC DISPLAY POOL TANK PROTECTION HEATER SUPPORT PROGRAM HEATER PUMP ROTATION CONTROL NIGHT COOLING HEAT DISCHARGE VACUUM COLLECTOR 10...

Страница 2: ......

Страница 3: ...E SOLAR CIRCUIT SYSTEM 25 15 3 USER PARAMETERS 26 15 4 SERVICE PARAMETERS 26 15 5 HEAT YIELD GRAPH 27 15 6 NETWORK SETTINGS 27 INSTALLATION MANUAL 29 16 TECHNICAL DATA 30 16 1 ELEMENTS OF THE SET 30 1...

Страница 4: ...person who read and understood this manual Use only in heating systems that are set up in accordance with valid regulations Electric system to which the controller is connected must be protected with...

Страница 5: ...with the above crossed bin symbol it means that it meets requirements of the European Directive 2002 96 EC It is recommended to know your local electric and electronic products disposal system It is r...

Страница 6: ......

Страница 7: ...OPERATING MANUAL PCSol 300...

Страница 8: ...e during controller operation when you keep the encoder pressed for 3 seconds it will cause exit to the main screen All controller settings are made through menu system MENU is recalled by pressing en...

Страница 9: ...The changed value will be confirmed when you press the knob again and you may select other setting After edition in submenu you may select the following by pressing on selection OK Confirms changes a...

Страница 10: ...hich the controller controls H output heater or other additional heat source When you switch off the temperature value in value edition box the time program will be set off and the controller will use...

Страница 11: ...disable circulation Value sch will activate time program for circulation 9 MENU ALARMS Access The controller may alarm on any irregularities in operation The controller has an intelligent alarm functi...

Страница 12: ...algorithm stops DHW reservoir loading 6 T3 sensor malfunction Alarm informs on incorrect operation or damage to T3 sensor Check connections for continuity connect or short circuit eliminate in sensor...

Страница 13: ...ed description of the options parameters is included in installation part of the manual Password 0000 will display submenu parameters only for reading 10 1 Restoring factory settings This menu allows...

Страница 14: ...rned off when Time Out has elapsed This function is useful to find the controller in dark rooms Encoder knob light pulsation will be also performed after the controller is switched off 11 2 Operation...

Страница 15: ...nu will not display heat output icon and the function may not be entered The controller logs data on recovered energy from last 14 days in the form of bar chart Fig 12 1 Heat output screen Energy tota...

Страница 16: ...DHW reservoir temperature T2 sensor to which the controller will be cooling the reservoir during night cooling function When the temperature drops to the one specified for Night cooling OFF the contro...

Страница 17: ...p to the temperature of TDHWmin Functioning of H output depends also on eco function set up as described in Adjustment menu TDHWmin temperature is set through main menu item TDHWmin List of settings i...

Страница 18: ...art reducing the pump speed until the difference between T1 and T2 reaches the value specified as dToffDHW If the difference between T1 and T2 is between the values dTonDHW dToffDHW the controller wil...

Страница 19: ...ture preset of hysteresis respectively HP1 for P1 pump and HP2 for P2 pump Eventually when the temperature at the collector sensor T1 will reach critical value TCOLcr Then the controller will allow sw...

Страница 20: ...t affect the controller operation If the parameter is set as NO the controller will not alarm when TCOLcr temperature is exceeded at the collector sensor 13 8 Solar thermal scheme G Loading of DHW res...

Страница 21: ...reaches the value specified as dToffDHW If the difference between T3 and T2 is between the values dTonDHW dToffDHW the controller will calculate and set the pump speed proportionally When dToffDHW is...

Страница 22: ...said difference between T1 and T2 drops below dTonDHW the controller will start reducing the pump speed until the difference between T1 and T2 reaches the value specified as dToffDHW If the differenc...

Страница 23: ...temperature on T2 sensor to which the regulator will be cooling down the container if night cooling function is enabled and Cooling temp ON temperature is exceeded between 000 500 TCOLkr alarm Enabli...

Страница 24: ...ff night cooling mode active from 0000 0500 Night cooling ON temperature of DHW tank read out of T2 sensor upon excess of which the regulator will activate night cooling mode at 000 provided that nigh...

Страница 25: ...over a Wi fi or LAN network The interface is operated by an ordinary search engine installed in any stationary and mobile communication devices 15 1 Basic data reading Fig 15 1 WWW interface tiles 15...

Страница 26: ...26 15 3 User parameters Fig 15 3 WWW interface user parameters 15 4 Service parameters Fig 15 4 WWW interface service parameters...

Страница 27: ...27 15 5 Heat yield graph Fig 15 5 WWW interface heat yield graph 15 6 Network settings Fig 15 6 WWW interface network settings screen...

Страница 28: ......

Страница 29: ...INSTALLATION MANUAL PCSol 300...

Страница 30: ...which heat output is not counted 17 INSTALLATION OF PCSol 300 The controller is designed for operation in the environment where only dry conductive contaminations may be present 2 degree of contamina...

Страница 31: ...rotection is ensured suitably to environmental conditions dust and water access is prevented permissible operating temperature is not exceeded for the controller 40 C air exchange inside casing is all...

Страница 32: ...cuits 0 75 1mm2 Low voltage circuits 0 25 0 75mm2 For installations with bare wire cables the maximal size is 1 5mm2 For good connection between the terminal and cable insulation and sleeve free lengt...

Страница 33: ...7 6 Connection of pumps Pump P2 is connected analogically as pump P1 Fig 17 7 Electro valve connection The connection shown in fig 17 7 requires electro valve coil adjusted to 230 voltage 17 2 3 Tempe...

Страница 34: ...sulating material so that there is sufficient temperature convection to the sensor Fig 17 9 Sensor installation on pipe surface 17 2 5 Output H connection Output H is adapted to connect relay supplied...

Страница 35: ...tion of rotations are connected via a relay and its contacts to relevant terminals Status relations on H outlet and respective direction of the valve switching are presented in application schemes Cha...

Страница 36: ...to the Internet in two ways over Wi fi to the local access point directly through Ethernet cable for LAN network The most convenient way of connection is recommended Both ways offer the same operation...

Страница 37: ...roller to count heat output install additional CT6 sensor on the outlet of lower pipe coil from DHW reservoir and connect to T4 input or T3 for Basic The sensor must be installed possibly near the con...

Страница 38: ...t will disable reservoir extra heating function How to connect H output to a heater via a relay is presented in details in section 17 2 5 Fig 18 2 Application scheme B Installation notes 1 For the con...

Страница 39: ...t The sensor must be installed possibly near the connector pipe 2 T3 sensor shows temperature in upper part of the reservoir its connection is not required 3 Circulation pump is connected to H output...

Страница 40: ...contact current not lower than the current of the circulation pump It is recommended to use relays with two switching tracks see details in section 17 2 5 Output H Setting notes 1 Do not set HP2 valu...

Страница 41: ...t 2 Circulation pump is connected to H output through a relay with contact current not lower than the current of the circulation pump It is recommended to use relays with two switching tracks see deta...

Страница 42: ...s near zero switching time set minimal value for tVALVE 3 When the circuits are being switched tVALVE time the collector pump is not working and the circuit receives no heat Pay attention to collector...

Страница 43: ...boiler Fig 18 7 Application scheme G Installation notes 1 Circulation pump is connected to H output through a relay with contact current not lower than the current of the circulation pump It is recomm...

Страница 44: ...troller to count heat output install additional CT6 sensor on DHW reservoir lower pipe coil and connect it to T4 input The sensor must be installed possibly near the connector pipe 3 Circulation pump...

Страница 45: ...losses incurred in the collector exchanger section will prevent starting of P2 pump even at high temperatures in the collector This setting must be selected specifically to each installation 3 During...

Страница 46: ...it is required to install additional CT6 sensor directly on the return from the DHW reservoir lower pipe coil and connect it to T4 measurement input 2 Circulation pump is connected to H output throug...

Страница 47: ...instructions 1 Two additional CT6 sensors are required for the application schema 2 Connect the circulation pump to H output via a transmitter with connector voltage not lower than circulation pump v...

Страница 48: ...enable calculation of heat yield by the regulator install additional CT6 type sensor at the outlet of lower pipe coil from DHW tank and connect it to T4 input The sensor should be mounted as close as...

Страница 49: ...a service password Fig 20 1 User login screen To login place cursor in selected digit by its rotating then press the button When the digit is blinking rotate the encoder to change its value Confirm t...

Страница 50: ...ical temperature Temperature which regardless of reaching reservoir preset TsDHW or pool preset TsPOOL will start the collector pump at 100 capacity in order to discharge heat from the collector It wi...

Страница 51: ...atically move sensor s characteristics to compensate the effect of additional resistance When you enter menu the controller displays current values of temperature corrections If the controller display...

Страница 52: ...collector function on off The function principle of operation is described in section 20 3 1 Detect level setting that defines how much the collector temperature must rise at started vacuum collector...

Страница 53: ...used as per IEC 60127 standard An example of a fuse meeting the requirements is Schurter MXT 250 time delay fuse To replace open controller s enclosure and replace burnt fuse with a new one Fig 21 1...

Страница 54: ......

Страница 55: ......

Страница 56: ...SALUS Controls ul Bielska 4a 43 200 Pszczyna Poland...

Отзывы: